background image

Stride Field I/O

3

SIO-MB04THMS User Guide, 1st Edition

DESCRIPTION OF MODBUS REGISTERS

40002 / 40003: 

FIRMWARE

Two read-only registers, containing the firmware version.

40007: 

NODE ID

Contains the Modbus address of the device; the values allowed are from 1 to 245 decimal.
This value must match the Modbus address of the connected Modbus device (data source).  
Default value: 1 Decimal (01 Hex). INIT value: 245 Decimal (F5 Hex).

40011: 

SYSTEM FLAGS

Contains the enable bits and system event identifiers. The following parameters are configurable:

Watchdog Event Enable

: this bit enables the Watchdog Event (0=Watchdog Disabled, 1 =Watchdog Enabled).  If the Watchdog 

is enabled and the Watchdog Timer (configured in register 40013) expires before this device receives a Modbus command, the 
green PWR LED blinks and the Watchdog Event bit is set to 1. This bit must be set in logic on power up.

Watchdog Event

: this bit is set to 1 when the Watchdog Timer expires before this device receives a Modbus command. This bit must 

be reset manually after a Watchdog event.  

Power Up Event

: this bit is forced to 1 at each time power is applied to the device to indicate that the device has been switched off 

or reset. With the setting of this bit as 0 (by the user) and checking its state, it is possible to know if a reset of the device has occurred 
(0 = reset not occurred; 1 = reset occurred).  This bit must be reset manually.

Bit

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Coil

-

-

-

-

-

163 162 161

-

-

-

-

-

-

-

-

Description

Watchdog Event enable 

Watchdog Event 

Power Up Event

40013: 

WATCHDOG TIMER

Contains the value of the Watchdog timer, in seconds. If the Watchdog is enabled and the device doesn’t receive a command before 
this timer expires, the Watchdog bit will be set to 1 (see the description of “System Flags”). Default value: 10 (10 sec.).

40031: 

INPUT TYPE CHANNEL 0

This register shows the type of sensor configured for this input (see “Input Type Table”).  
Default: Tc K (05 Hex)

Bit

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Description

Input Type #0

40032: 

INPUT TYPE CHANNEL 1

This register shows the type of sensor configured for this input (see “Input Type Table”).  
Default: Tc K (05 Hex)

Bit

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Description

Input Type #1

INPUT TYPE TABLE

Type

Value (Hex) Value (Dec)

Disabled

00h

0

250mV

01h

1

TC J

04h

4

TC K

05h

5

TC R

06h

6

TC S

07h

7

TC T

08h

8

TC B

09h

9

TC E

0Ah

10

TC N

0Bh

11

Summary of Contents for SIO-MB04THMS

Page 1: ...Manual Number SIO MB04THMS UG Field I O SIO MB04THMS USER GUIDE Temperature Input Module thermocouple 4 channel in ...

Page 2: ... Type Channel 0 R W 40032 Input Type Channel 1 R W 40033 Input Type Channel 2 R W 40034 Input Type Channel 3 R W 40041 Analog Input 0 Ch0 RO 40042 Analog Input 1 Ch1 RO 40043 Analog Input 2 Ch2 RO 40044 Analog Input 3 Ch3 RO 40050 Break Status RO 41241 Offset Channel 0 R W 41242 Offset Channel 1 R W 41243 Offset Channel 2 R W 41244 Offset Channel 3 R W SUPPORTED MODBUS FUNCTION CODES Function Desc...

Page 3: ...Stride Field I O 2 SIO MB04THMS User Guide 1st Edition PRODUCT LABEL AND WIRING DIAGRAM Terminal block pinouts and wiring diagrams are printed on the side of the module as shown below ...

Page 4: ...each time power is applied to the device to indicate that the device has been switched off or reset With the setting of this bit as 0 by the user and checking its state it is possible to know if a reset of the device has occurred 0 reset not occurred 1 reset occurred This bit must be reset manually Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 Coil 163 162 161 Description Watchdog Event enab...

Page 5: ...red with two implied decimal places for mV inputs For example Input type set as Tc 246 stored in the register indicates 24 6 C Input type set as mV 24656 stored in the register indicates 246 56 mV NOTE When INIT mode is active the analog input measurements are not updated 40050 BREAK STATUS When a break condition is detected e g broken sensor disconnected cable or over temperature the bit correspo...

Page 6: ...slightly Enter the Username and Password Default username admin Default password password Click Login to access the device as follows Note that all pages include a Logout button to quit and return to the login page The device interface includes five configuration categories as shown by the navigation menu on the left of the screen on the next page Hovering over a navigation button will display a t...

Page 7: ... gateway A default gateway allows this device to communicate with devices on another subnet Socket Timeout set the timeout time in minutes the device will close its TCP connection if it does not receive a command within this time period Click Save to apply and store the modified parameters Wait for the device to reset After modifying the network settings you will need to use the updated IP address...

Page 8: ...atchdog event 0 Watchdog disabled 1 Watchdog enabled Timeout ref Watchdog timer register set the value in seconds of the Watchdog timer Watchdog Event ref System Flags register this flag signals that the Watchdog condition has occurred 0 Normal condition 1 Alarm condition Power up Event ref System Flags register this flag is forced to 1 at each power on and indicates that the device has been switc...

Page 9: ...Upgrade opens a dialog to enter credentials select a file from the local PC and proceed with the update Firmware Version shows the firmware version loaded on the device WebPage Version shows the version of the web based user interface loaded on the device Do not disconnect power from the device during the upgrade process ...

Page 10: ...1st Edition Username and Password Set the user name and password Username set the user name to access the device Default admin Password set the password to access the device Default password Click Save to apply and store the modified parameters ...

Page 11: ...cted to the input A channel can be disabled by selecting Disabled as its input type Value ref Analog Input registers shows the current value of each analog input Break ref Break register indicates the connectivity status of the sensor If a sensor is disconnected a wire is broken or the sensor is over temperature a red indicator is shown under the break column at that channel Offset sets an offset ...

Page 12: ...er Open a browser and type 192 168 1 174 or the DHCP assigned address in the address field Browse through the user interface to view configuration settings and data or change configuration settings When all changes are complete and saved disconnect power from the device Remove the connection shorting the INIT and VS terminals Apply power to the device and access it from a browser using the configu...

Reviews: