MFC Kit Instructions
5.0 PQconnect Option
44
Write Parameters:
Table 20: Network Interface INPUT/Setpoint Register Map
Parameter Name
I/O Reg
Address
Offset
Direction
Format and
Examples
Description
USER_STATE_REQ
500
Input
0 = Initialization
9 = Save current
values to flash
150 = Load values
from Flash
255 = Restore Defaults
to Flash
Note that defaulting the flash
will clear all calibration data
and require that the calibration
procedure be re-run..
TRACE_GO_DONE
501
Input
0 = Capture Done
1 = Start Capture
Update trace data points for
waveforms
PARAM_KEY_A
502
Input
Enter Key A
Read/write parameters under
Tech Access
PARAM_KEY_B
503
Input
Enter Key B
RELAY_MIN_ON_TIME
505
Input
Output Relay Minimum
status detection active
time in seconds
Range 1 to 3600
seconds. Default 10
seconds
Minimum time output relay will
indicate an active status
detection.
TRACE_RESOLUTION_RANGE_HYST
508
Input
Fundamental period
steps of 30uS, Range
0 to 500, Default 5.
Waveform time base
resolution range hysteresis.
The higher the number the
less the waveform will adjust
its time scale based on the
fundamental frequency of the
filter output.
RATED_VOLTAGE
521
Input
4800 = 480 Vrms
Range = 120 to 690
Vrms, Default of 4800
Filter rated voltage in Volts
RMS Line to Line
OUTPUT_RELAY_1_ENABLE
540
Input
For each bit position:
0 = Detection disabled
1 = Detection enabled
Default = 32888 ( High
THVD Phase A, B, C,
Thermal SW1, and
CPU error enabled).
To Enable desired fault
detections, enter bit
mask from table by
converting to decimal
Range: 0 to 65535
This value is a bit mask where
individual bits are set to
indicate a detection is active.
For a description of bit
positions see Table 15
Example: Enabling all fault
conditions is 1111 1111 1111
1111 in binary or 65535
decimal. *
Reference Fault codes
Table 19
OUTPUT_RELAY_2_ENABLE
550
Input
For each bit position:
0 = Detection disabled
1 = Detection enabled
Default = 64 (Theral
SW1 enabled)
To Enable desired fault
detections, enter bit
mask from table by
converting to decimal
Range: 0 to 65535
This value is a bit mask where
individual bits are set to
indicate a detection is active.
For a description of bit
positions see Table 15
Example: Enabling all fault
conditions is 1111 1111 1111
1111 in binary or 65535
decimal.*
Reference status conditions
Table 19
MB_SLAVE_ADDRESS
600
Input
DEAFAULT =
10
Range 0 to 255
Modbus RTU Device Slave
Address *