Parameterization and configuration
TR-Electronic GmbH 2010, All Rights Reserved
Printed in the Federal Republic of Germany
Page 174 of 183
TR - ELA - BA - DGB - 0016 - 04
01/20/2017
8.2.10 Measuring system diagnostics
8.2.10.1 Object 6500h
– Operating status
This object indicates whether rising or falling position values are output when the
magnet moves towards the end of the rod.
Unsigned16
Bit
Function
Bit = 0
Bit = 1
0-1
reserved
2
Scaling function
-
always 1, enabled
3
Code Sequence
increasing
decreasing
4 - 15 reserved
8.2.10.2 Object 6501h
– Measuring step
This object indicates the measuring step that is output by the measuring system. The
measuring step is given in nm (0.001 µm).
Example: 1 µm = 00 00 03 E8 h
Unsigned32
Measuring step
Byte 0
Byte 1
Byte 2
Byte 3
2
7
to 2
0
2
15
to 2
8
2
23
to 2
16
2
31
to 2
24
8.2.10.3 Object 6503h
– Alarms
Additionally to the
“Emergency Message”, this object provides further alarm
messages. An alarm is set if a malfunction in the measuring system could lead to an
incorrect position value. If an alarm occurs, the according bit is set to logical high until
the alarm is cleared and the measuring system is able to provide an accurate position
value.
Unsigned16
Bit
Function
Bit = 0
Bit = 1
0
Position error
No
Yes
1-15
Reserved for further use
Position error
The bit is set, if the measuring system could not detected a magnet.