Programming Basic Instructions
5-2 | CFW500
5
5.3 HMI
In the HMI group, you find parameters related to the showing of information on the display, backlight and password
of the HMI. See detailed description below of the possible settings of the parameters.
P0000 – Access to the Parameters
Adjustable
Range:
0 to 9999
Factory
Setting:
0
Properties:
Access Groups
via HMI:
Description:
Password input to release the access to the parameters. Once a password is saved in P0200, the access to
the parameters is only allowed if this password is set in P0000.
After setting P0000 with a password value, P0000 will show “1” or “0”, keeping the set password value hidden.
Where “1” releases the access to parameters and “0” locks the access to the parameters.
NOTE!
The access to the parameters and P0000 is cleared together with the powering down of the inverter.
P0200 – Password
Adjustable
Range:
0 = Inactive
1 = Active
1 to 9999 = New Password
Factory
Setting:
0
Properties:
Access Groups
via HMI:
HMI
Description:
It allows activating the password (by inserting a new value) or disabling it. For further details regarding the use
of this parameter, refer to
Table 5.2:
Required procedure for each kind of action
Action
Procedure
Activate password.
1. Set P0200 with the desired value for the password (P0200 = password).
2. After this procedure, the new password is active and P0200 is automatically adjusted for 1 (password
active).
(1)
Change password.
1. Set the current value of the password (P0000 = password).
2. Set the desired value for the new password in P0200 (P0200 = new password).
3. After this procedure, the new password is active and P0200 is automatically adjusted for 1 (password
active).
(1)
Disable password.
1. Set the current value of the password (P0000 = password).
2. Set inactive password (P0200 = 0).
3. After this procedure, the password is disabled.
(2)
Disable password.
1. Activate a factory default by means of P0204.
2. After this procedure, the password is disabled.
(2)
Notes:
(1)
It only allows changing the content of the parameters when P0000 is equal to the value of the password.
(2)
It is allowed to change the content of the parameters and P0000 is inaccessible.
Summary of Contents for CFW500 V1.8X
Page 2: ......
Page 4: ......
Page 8: ...Contents...
Page 34: ...General Information 2 4 CFW500...
Page 38: ...About the CFW500 3 4 CFW500 3...
Page 42: ...HMI and Basic Programming 4 4 CFW500 4...
Page 52: ...Programming Basic Instructions 5 10 CFW500 5...
Page 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Page 76: ...Available Motor Control Types 8 4 CFW500 8...
Page 84: ...V f Scalar Control 9 8 CFW500 9...
Page 170: ...Communication 17 8 CFW500 17...