Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1 = 1
0000h…FFFFh
0.00 A / real32
Sets a custom motor current fault limit.
The drive automatically sets an internal motor current
limit according to the drive hardware. The internal limit
is appropriate in most cases, but this parameter can
be used to set a lower current limit, for example, to
protect a permanent magnet motor from
demagnetization.
Note: The limit defines the maximum peak current of
one phase.
With this parameter at 0.0 A, only the internal limit is
in force.
Overcurrent fault
limit
31.42
- / -
Custom motor current fault limit. For scaling, see
parameter
0.00 ... 30000.00 A
Coast / uint16
Selects the stop mode when a non-critical fault occurs.
Fault action
31.54
0
The drive coasts to a stop.
Coast
1
The drive follows the ramp specified for an emergency
stop in parameter
.
Emergency ramp
Fault / uint16
Selects how the drive reacts when the communication
to an I/O extension module fails.
Ext I/O comm loss
event
31.55
0
No action taken.
No action
1
The drive generates a warning,
.
Warning
2
The drive trips on a fault,
Fault
Fault / uint16
(Only visible when IGBT supply unit control activated
by
)
Selects how the supply unit reacts when an earth fault
or current unbalance is detected.
LSU earth fault
31.120
0
No action taken.
No action
1
The supply unit generates a warning,
Warning
2
The supply unit trips on a fault,
Fault
Fault / uint16
(Only visible when IGBT supply unit control activated
by
)
Selects how the supply unit reacts when a supply phase
loss is detected.
LSU supply phase
loss
31.121
0
No action taken.
No action
1
The supply unit trips on a fault,
.
Fault
Parameters 327
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...