Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
- / real32
Displays the temperature measured through the sensor
input of interface module 2. The unit (°C or °F) is
selected by parameter
Note: With a PTC sensor, the unit is ohms.
Note: This parameter is read-only.
Module 2
temperature
91.6
- / -
Temperature measured through interface module 2.
0.0 ... 1000.0 °
Done / uint16
Validates any changed encoder interface module
parameters. This is needed for any parameter changes
in groups 90…93 to take effect.
After refreshing, the value reverts automatically to
.
•
Permanent magnet motors only: The drive will
perform a fresh autophasing routine (see page
) at next start if the motor feedback encoder
settings have been changed.
•
The parameter cannot be changed while the drive
is running.
Encoder parameter
refresh
91.10
0
Refreshing done.
Done
1
Refreshing.
Refresh
None / uint16
Defines the type of the module used as interface
module 1.
Module 1 type
91.11
0
None (communication disabled).
None
1
FEN-01.
FEN-01
2
FEN-11.
FEN-11
3
FEN-21.
FEN-21
4
FEN-31.
FEN-31
5
FSE-31.
FSE-31
2 / uint16
Specifies the slot (1…3) on the control unit of the drive
into which the interface module is installed.
Alternatively, specifies the node ID of the slot on an
FEA-03 extension adapter.
Module 1 location
91.12
1 = 1 / 1 = 1
Slot 1 = 1; Slot 2 = 2; Slot 3 = 3
4…254: Node ID of the slot on the FEA-03 extension
adapter
1...254
None / uint16
Defines the type of the module used as interface
module 2.
Module 2 type
91.13
0
None (communication disabled).
None
1
FEN-01.
FEN-01
2
FEN-11.
FEN-11
3
FEN-21.
FEN-21
4
FEN-31.
FEN-31
5
FSE-31.
FSE-31
490 Parameters
Summary of Contents for ACS880 N5700 Series
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Page 2: ......
Page 4: ......
Page 22: ...22 ...
Page 28: ...28 ...
Page 32: ...32 ...
Page 60: ...60 ...
Page 546: ...546 ...
Page 604: ...604 ...
Page 626: ...626 ...
Page 640: ...640 ...
Page 660: ...660 ...