Access from the user program
KL2751/KS2751, KL2761/KS2761
43
Version: 3.1.0
R32: Feature register
The feature register specifies the terminal's configuration.
Bit
R32.15
R32.14
R32.13
R32.12
R32.11
R32.10
R32.9
R32.8
Name
-
-
-
-
-
-
-
-
Bit
R32.7
R32.6
R32.5
R32.4
R32.3
R32.2
R32.1
R32.0
Name
-
-
-
-
DimRamp disWatchdog -
enUserScale
Legend
Bit
Name
Description
Default
R32.1
5 -
R32.4
-
reserved
R32.3 DimRamp
0
bin
Dimming ramp relative:
The time in register R35 relates to the entire process data range
(0
dec
- 32767
dec
). This means that the dimmer terminal requires this
time to control from "off" (0
dec
) to full scale control (32767
dec
).
0
bin
1
bin
:
The time in register R35 relates to the current process data change.
This means that the dimmer terminal requires this time in order to
execute the current brightness change.
R32.2 disWatchdog
1
bin
Internal watchdog (time adjustable) deactivated
0
bin
R32.1 -
reserved
R32.0 enUserScale
1
bin
User scaling active (see
0
bin
R33: User scaling - offset
The offset of the user scaling when the user scaling (
bin
) is enabled is entered in this register
(default: 0).
R34: User scaling - gain
The gain of the user scaling when the user scaling (
bin
) is enabled is entered in this register.
Example values:
128
dec
= 0x80 = factor 0.5
256
dec
= 0x100 = factor 1.0 (default)
512
dec
= 0x200 = factor 2.0
R35: Ramp time
This register specifies the time required
• to ramp up from 0 to 32767 (full scale control of the angle) (when R32.3 = 0
bin
) or
• to execute the current brightness change (when R32.3 = 1
bin
).
0
dec
: 50 ms
1
dec
: 100 ms
2
dec
: 200 ms
3
dec
: 500 ms (default)
4
dec
: 1 s
5
dec
: 2 s
6
dec
: 5 s
7
dec
: 10 s
R36: Watchdog Timeout
This register specifies the timeout in the event of a fieldbus error. The unit is 10 ms (default: 10
dec
= 100 ms).