Key
Bit
Name
Description
default
R32.15...
R32.12
SensorType 0000
bin
PT1000
0
bin
0001
bin
NI1000
0010
bin
RSNI1000 (note: different characteristic curve, similar to
NI1000, but with 1000 Ω at 0 °C and 1500 Ω at 100 °C)
R32.11
disChannel
0
bin
Channel switched on
0
bin
1
bin
Channel switched off
R32.10…
R32.6
-
reserved
0
bin
R32.5
Resolution
R32.5=1: high resolution 1/100°C (default for KL3208-0010)
R32.5=0: standard resolution 1/10°C
0/1
R32.3/4
-
reserved
0
bin
R32.2
DisWdTimer Disable Watchdog Timer
0
bin
R32.1
enManScal
0
bin
Manufacturer scaling is not active
0
bin
1
bin
Manufacturer scaling is active
R32.0
enUsrScal
0
bin
User scaling is not active
0
bin
1
bin
User scaling is active
R33: User scaling – offset
This register contains the offset of the user scaling. User scaling can be activated in the feature register via
bit
R34: User scaling – gain
This register contains the gain of the user scaling. User scaling can be activated in the feature register via bit
R37: Filter constant of the A/D converter
Value in R37
First Notch
Conversion time
0x0000
25 Hz
250 ms
0x0050
100 Hz
65 ms
0x00A0
50 Hz
125 ms
0x0140
25 Hz
250 ms
0x0280
12.5 Hz
500 ms
R39: Further elements
Register R39 is supported by KL3208-0010 from firmware version 1C and hardware version 01 (Default: 0
dec
)
Setting R39 increases the conversion time to one second per channel
As soon as register R39 is not equal to 0 for one channel of the terminal, the conversion time for all
channels is increased to about 1 second per channel, automatically and irrespective of the sensor
type, in order to optimize the measuring accuracy. The conversion time for all channels can be com-
monly set via register R40 of channel 1. A reduction is not recommended due to loss of accuracy.