22
5.6
Controlling the Outputs
The following table shows you the AT commands to control or read out the inputs and outputs:
Output / function
Command
DIG_OUT configuration
AT^SCPIN=1,3,1,0
DIG_OUT High (VCC voltage)
AT^SSIO=3,1
DIG_OUT Low (ca. 1.6 Volts)
AT^SSIO=3,0
Yellow LED configuration
AT^SCPIN=1,5,1,0
Yellow LED on
AT^SSIO=5,1
Yellow LED off
AT^SSIO=5,0
Red LED configuration
AT^SCPIN=1,6,1,0
Red LED on
AT^SSIO=6,1
Red LED off
AT^SSIO=6,0
ANALOG-IN read out value
AT^SRADC=1
The ANALOG-IN-value needs to be calculated using the return value of the read out command.
Therefore use the following formula:
V
ANALOG-IN
= (return_value / 6.8) x 204.8 (Result is in mill volts)
5.7
Power consumption during Regular Operation
The following table shows you the power consumption of the CT63 NG Terminal in different modes.
Please refer to Table 7 and Table 8 for details of power consumption in Low Power Mode.
[mA] @ 5V
[mA] @ 12V
[mA] @ 24V
[mA] @ 32V
Modem is off
(DTR low, no TO-IN)
0,01
0,14
0,26
0,35
CT63 idle mode
(Modem is on, logged into GSM
network, serial interface is discon-
nected)
22,2
10,4
8,8
6,7
Table 10: Power consumption in standby, idle and low power mode