iom-clicsa-cf-eng
www.clima-flex.com
33
Mapping Table
Index
S
ize Acronym
Data
Type
Min
Value
Max
Value R/W
Init
Value UoM Description
58
1
DevRotReq_
Comp2Circ1
BOOL
R/W
Request comp.2 circ.1 by DeviceRotation
59
1
ClrH
BOOL
R/W FALSE
ClrH - Delete alarms log (0=No, 1=Yes)
60
1
UnitOn_Slv
BOOL
R/W
Unit ON/OFF status (0=OFF, 1=ON) sent to Secondary board
61
1
UsrPmp2_On_Slv
BOOL
R/W
Command to manage user pump 2 (Secondary board)
62
1
AFreezeHeat_Slv
BOOL
R/W
Command to manage the frost heater (Secondary board)
63
1
Hd05
BOOL
R/W FALSE
Hd05 - Enable unit ON/OFF command by BMS net (0=Disabled, 1=Enabled)
64
1
BmsOnOff
BOOL
R/W
Unit On/Off command from BMS (0=OFF, 1=ON)
65
1
HeatCool_Slv
BOOL
R/W
Unit in cooling mode sent to secondary board (0=Heating, 1=Cooling)
66
1
P016
BOOL
R/W FALSE
P016 - Oil equalisation solenoid valve circ.1 output logic (0=NC, 1=NO)
67
1
P017
BOOL
R/W TRUE
P017 - Enable oil equalisation function (0=OFF, 1=ON)
68
1
P018
BOOL
R/W FALSE
P018 - Enable oil recovery function (0=OFF, 1=ON)
69
1
P034
BOOL
R/W FALSE
P034 - Enable cranckcase heater (0=OFF, 1=ON)
70
1
Al_SrsUnit_StopSlv
BOOL
R/W
Main sends Serious alarm to stop Secondary
71
1
CompCfg_BLDC.
En_VaporInjection
BOOL
R/W FALSE
#N/D
72
1
SlaveTyp_OnOff BOOL
R/W FALSE
Secondary type (0=Secondary connected to CORE-1 with Rotation,
1= Secondary connected to CORE-0 with EasyRot for ON/OFF)
73
1
ManInstDef_PWRP
BOOL
R/W
Request default installation of Power+ circ.1
74
1
MC_UnitTyp
BOOL
R/W FALSE
MC unit(0= NO, 1= YES)
75
1
En_uC2SE
BOOL
R/W FALSE
#N/D
76
1
C051
BOOL
R/W FALSE
C051 - Low press. switch input logic (0=N.C., 1=N.O.)
77
1
F003
BOOL
R/W FALSE
F003 - Evaporator number uC2SE (0=1, 1=2)
78
1
F020
BOOL
R/W TRUE
F020 - Remote compressor command input logic (0=N.C., 1=N.O.)
79
1
F007
BOOL
R/W FALSE
F007 - S4 probe fi tted on source exchanger [uCH2SE] (0= NO, 1=YES: in
CH read cond., in HP read evap.)
80
1
U078
BOOL
R/W FALSE
U078 - Enable burst function (0=Disabled, 1=Enabled)
81
1
F016
BOOL
R/W FALSE
F016 - Heaters active during defrost (0=OFF, 1=ON)
82
1
F017
BOOL
R/W FALSE
F017 - User fan device activation mode (0=Always ON, 1=ON by control)
83
1
UsrHeater1
BOOL
R/W FALSE
UsrHeater1 - User heater 1 status
84
1
F011
BOOL
R/W FALSE
F011 - Heater output logic (0=N.O., 1=N.C.)
85
1
F023
BOOL
R/W FALSE
F023 - Correspondence D.I. to D.O. compressors (for MC units only)
(0=FALSE, 1=TRUE)
87
1
UsrFanON
BOOL
R/W FALSE
UsrFanON - User fan ON
88
1
FC_Agree
BOOL
R/W
Free cooling condition exists (0=FC not possible; 1=FC possible)
89
1
En_SrcRetTempPrb
BOOL
R/W FALSE
En_SrcRetTempPrb - Connected source return temperature probe
90
1
WaitOtherDevCirc1_
SmartOpnExV
BOOL
R/W
0
91
1
LowNoiseActive
BOOL
R/W FALSE
Low noise function active
92
1
S073
BOOL
R/W FALSE
S073 - Compressor status at defrost in (0 : Minimum speed, 1: OFF)
93
1
U082
BOOL
R/W FALSE
U082 - Frost measurement type (0=ON EVAP., 1=ON WATER)
94
1
F028
BOOL
R/W FALSE
F028 - Air heating: Control temp. probe for user heaters (0=ROOM,
1=DELIVERY)
95
1
AFreezeHeatUsr
BOOL
R/W
User frost heater status
97
1
AFreezeHeatSrc
BOOL
R/W
Source frost heater status
96
1
S066
BOOL
R/W TRUE
S066 - Source water fl ow type (0=Independent, 1=Common)
117
1
S074
BOOL
R/W FALSE
S074 - Source fan/pmp alarm input logic (0=N.C., 1=N.O.)
121
1
U093
BOOL
R/W FALSE
U093 - Flow alarm management
Holding Register
Index
S
ize Acronym
DataType
Min
Value
Max
Value R/W
Init
Value UoM
Description
0
2
Ha00
DATE_
AND_TIME
R/W 0
Ha00 - New date and time to set on the controller’s internal
clock
2
1
U000
UINT(0..999)
R/W 99
HOUR
U000 - User pump 1 maintenance hour threshold (x100)
3
1
U002
UINT(0..2)
R/W 0
U002 - User pump 1/fan manual mode (0=AUTO, 1=OFF, 2=ON)
4
1
U003
UINT(0..999)
R/W 0
HOUR
U003 - User pump 2 maintenance hour threshold (x100)
5
1
U005
UINT(0..2)
R/W 0
U005 - User pump 2 manual mode (0=AUTO, 1=OFF, 2=ON)
6
1
U083
USINT(0..3)
R/W 0
U083 - Automatic changeover type
7
2
U006
REAL
R/W 5
CELSIUS
U006 - Cool set point low limit
9
2
U007
REAL
R/W 20
CELSIUS
U007 - Cool set point high limit
11
2
U008
REAL
R/W 30
CELSIUS
U008 - Heat set point low limit
13
2
U009
REAL
R/W 45
CELSIUS
U009 - Heat set point high limit
15
2
U011
REAL
R/W 25
CELSIUS
U011 - Start temp. for cool set point compensation
17
2
U012
REAL
R/W 10
CELSIUS
U012 - End temp. for cool set point compensation
19
2
U013
REAL
R/W 5
DELTAKELVIN U013 - Max compensation for cool set point
21
2
U014
REAL
R/W 5
CELSIUS
U014 - Start temp. for heat set point compensation
23
2
U015
REAL
R/W -10
CELSIUS
U015 - Outside temp. diff . for heat set point compensation
25
2
U016
REAL
R/W 5
DELTAKELVIN U016 - Max compensation for heat set point
27
1
U018
UINT
R/W 0
HOUR
Time band hours
28
1
U019
UINT
R/W 0
MINUTE
Time band minutes
29
1
U020
UINT
R/W 0
HOUR
Time band hours
30
1
U021
UINT
R/W 0
MINUTE
Time band minutes
31
2
U023
REAL
R/W 10
CELSIUS
U023 - 2nd cool set point
33
2
U024
REAL
R/W 35
CELSIUS
U024 - 2nd heat set point
35
1
U025
USINT(0..2)
R/W 0
U025 - Analogue set point input type (0=0-5V, 1=0-10V,
2=4-20mA)
36
1
F008
UINT(0..999)
R/W 10
SECOND
F008 - Antifrezee alarm delay
37
2
U026
REAL
R/W 5
CELSIUS
U026 - Remote set point min value
39
2
U027
REAL
R/W 35
CELSIUS
U027 - Remote set point max value
41
1
S023
UINT
R/W 0
HOUR
Time band hours
42
1
S024
UINT
R/W 0
MINUTE
Time band minutes