Mapping Table 

Index

S

ize Acronym

Data

Type

Min

Value

Max

Value R/W

Init

Value UoM Description

58

1

DevRotReq_
Comp2Circ1

BOOL

R/W

Request comp.2 circ.1 by DeviceRotation

59

1

ClrH

BOOL

R/W FALSE

ClrH - Delete alarms log (0=No, 1=Yes)

60

1

UnitOn_Slv

BOOL

R/W

Unit ON/OFF status (0=OFF, 1=ON) sent to Secondary board

61

1

UsrPmp2_On_Slv

BOOL

R/W

Command to manage user pump 2 (Secondary board)

62

1

AFreezeHeat_Slv

BOOL

R/W

Command to manage the frost heater (Secondary board)

63

1

Hd05

BOOL

R/W FALSE

Hd05 - Enable unit ON/OFF command by BMS net (0=Disabled, 1=Enabled)

64

1

BmsOnOff

BOOL

R/W

Unit On/Off  command from BMS (0=OFF, 1=ON)

65

1

HeatCool_Slv

BOOL

R/W

Unit in cooling mode sent to secondary board (0=Heating, 1=Cooling)

66

1

P016

BOOL

R/W FALSE

P016 - Oil equalisation solenoid valve circ.1 output logic (0=NC, 1=NO)

67

1

P017

BOOL

R/W TRUE

P017 - Enable oil equalisation function (0=OFF, 1=ON)

68

1

P018

BOOL

R/W FALSE

P018 - Enable oil recovery function (0=OFF, 1=ON)

69

1

P034

BOOL

R/W FALSE

P034 - Enable cranckcase heater (0=OFF, 1=ON)

70

1

Al_SrsUnit_StopSlv

BOOL

R/W

Main sends Serious alarm to stop Secondary

71

1

CompCfg_BLDC.
En_VaporInjection

BOOL

R/W FALSE

#N/D

72

1

SlaveTyp_OnOff BOOL

R/W FALSE

Secondary type (0=Secondary connected to CORE-1 with Rotation, 
1= Secondary connected to CORE-0 with EasyRot for ON/OFF)

73

1

ManInstDef_PWRP

BOOL

R/W

Request default installation of Power+ circ.1

74

1

MC_UnitTyp

BOOL

R/W FALSE

MC unit(0= NO, 1= YES)

75

1

En_uC2SE

BOOL

R/W FALSE

#N/D

76

1

C051

BOOL

R/W FALSE

C051 - Low press. switch input logic (0=N.C., 1=N.O.)

77

1

F003

BOOL

R/W FALSE

F003 - Evaporator number uC2SE (0=1, 1=2)

78

1

F020

BOOL

R/W TRUE

F020 - Remote compressor command input logic (0=N.C., 1=N.O.)

79

1

F007

BOOL

R/W FALSE

F007 - S4 probe fi tted on source exchanger [uCH2SE] (0= NO, 1=YES: in 
CH read cond., in HP read evap.)

80

1

U078

BOOL

R/W FALSE

U078 - Enable burst function (0=Disabled, 1=Enabled)

81

1

F016

BOOL

R/W FALSE

F016 - Heaters active during defrost (0=OFF, 1=ON)

82

1

F017

BOOL

R/W FALSE

F017 - User fan device activation mode (0=Always ON, 1=ON by control)

83

1

UsrHeater1

BOOL

R/W FALSE

UsrHeater1 - User heater 1 status

84

1

F011

BOOL

R/W FALSE

F011 - Heater output logic (0=N.O., 1=N.C.)

85

1

F023

BOOL

R/W FALSE

F023 - Correspondence D.I. to D.O. compressors (for MC units only) 
(0=FALSE, 1=TRUE)

87

1

UsrFanON

BOOL

R/W FALSE

UsrFanON - User fan ON

88

1

FC_Agree

BOOL

R/W

Free cooling condition exists (0=FC not possible; 1=FC possible)

89

1

En_SrcRetTempPrb

BOOL

R/W FALSE

En_SrcRetTempPrb - Connected source return temperature probe

90

1

WaitOtherDevCirc1_
SmartOpnExV

BOOL

R/W

0

91

1

LowNoiseActive

BOOL

R/W FALSE

Low noise function active

92

1

S073

BOOL

R/W FALSE

S073 - Compressor status at defrost in (0 : Minimum speed, 1: OFF)

93

1

U082

BOOL

R/W FALSE

U082 - Frost measurement type (0=ON EVAP., 1=ON WATER)

94

1

F028

BOOL

R/W FALSE

F028 - Air heating: Control temp. probe for user heaters (0=ROOM, 
1=DELIVERY)

95

1

AFreezeHeatUsr

BOOL

R/W

User frost heater status

97

1

AFreezeHeatSrc

BOOL

R/W

Source frost heater status

96

1

S066

BOOL

R/W TRUE

S066 - Source water fl ow type (0=Independent, 1=Common)

117

1

S074

BOOL

R/W FALSE

S074 - Source fan/pmp alarm input logic (0=N.C., 1=N.O.)

121

1

U093

BOOL

R/W FALSE

U093 - Flow alarm management

Holding Register

Index

S

ize Acronym

DataType

Min

Value

Max

Value R/W

Init

Value UoM

Description

0

2

Ha00

DATE_
AND_TIME

R/W 0

Ha00 - New date and time to set on the controller’s internal 
clock

2

1

U000

UINT(0..999)

R/W 99

HOUR

U000 - User pump 1 maintenance hour threshold (x100)

3

1

U002

UINT(0..2)

R/W 0

U002 - User pump 1/fan manual mode (0=AUTO, 1=OFF, 2=ON)

4

1

U003

UINT(0..999)

R/W 0

HOUR

U003 - User pump 2 maintenance hour threshold (x100)

5

1

U005

UINT(0..2)

R/W 0

U005 - User pump 2 manual mode (0=AUTO, 1=OFF, 2=ON)

6

1

U083

USINT(0..3)

R/W 0

U083 - Automatic changeover type 

7

2

U006

REAL

R/W 5

CELSIUS

U006 - Cool set point low limit

9

2

U007

REAL

R/W 20

CELSIUS

U007 - Cool set point high limit

11

2

U008

REAL

R/W 30

CELSIUS

U008 - Heat set point low limit

13

2

U009

REAL

R/W 45

CELSIUS

U009 - Heat set point high limit

15

2

U011

REAL

R/W 25

CELSIUS

U011 - Start temp. for cool set point compensation

17

2

U012

REAL

R/W 10

CELSIUS

U012 - End temp. for cool set point compensation

19

2

U013

REAL

R/W 5

DELTAKELVIN U013 - Max compensation for cool set point

21

2

U014

REAL

R/W 5

CELSIUS

U014 - Start temp. for heat set point compensation

23

2

U015

REAL

R/W -10

CELSIUS

U015 - Outside temp. diff . for heat set point compensation

25

2

U016

REAL

R/W 5

DELTAKELVIN U016 - Max compensation for heat set point

27

1

U018

UINT

R/W 0

HOUR

Time band hours

28

1

U019

UINT

R/W 0

MINUTE

Time band minutes

29

1

U020

UINT

R/W 0

HOUR

Time band hours

30

1

U021

UINT

R/W 0

MINUTE

Time band minutes

31

2

U023

REAL

R/W 10

CELSIUS

U023 - 2nd cool set point

33

2

U024

REAL

R/W 35

CELSIUS

U024 - 2nd heat set point

35

1

U025

USINT(0..2)

R/W 0

U025 - Analogue set point input type (0=0-5V, 1=0-10V, 
2=4-20mA)

36

1

F008

UINT(0..999)

R/W 10

SECOND

F008 - Antifrezee alarm delay

37

2

U026

REAL

R/W 5

CELSIUS

U026 - Remote set point min value

39

2

U027

REAL

R/W 35

CELSIUS

U027 - Remote set point max value

41

1

S023

UINT

R/W 0

HOUR

Time band hours

42

1

S024

UINT

R/W 0

MINUTE

Time band minutes

Summary of Contents for Clima-Flex CLIC STAND ALONE Series

Page 1: ...ion and Maintenance Manual CLIC STAND ALONE Series Air Cooled Scroll Compressor Chiller Water Generator Unit Model 25 TR Refrigerant HFC 410A 50 60 Hz IOM Group Chiller Part Number IOM CLIC STAND ALON...

Page 2: ...facility Safety Warning 4 General Description 5 Features Benefits 6 Installation and Application Information 8 Refrigeration Schematics 14 Dimensions and Weights Packaged Units 15 Refrigerant Charge...

Page 3: ...zed at least 12 hours before startup Chiller components EXV Sensors Transducers installed and wired properly Wiring complies with National Electrical Code and local codes See Notes Miscellaneous Yes N...

Page 4: ...ge breaker may result in electric shock or fire WARNING If refrigerant leaks from the unit there is a potential choking danger as the refrigerant will displace air in the immediate area Be sure to fol...

Page 5: ...Only H Heat Pump UNITS 1 Stand alone 2 2 units 3 3 units 4 4 units 5 5 units 6 6 units 7 7 units 8 8 units 9 units 10 10 units CONDENSER FAN A Axial Fixed ANTICORROSION C Coat in Condenser I Coat in...

Page 6: ...ipment comes with a 1 year major warranty after start up Our units use R410A refrigerant which is harmless to the ozone layer and is non toxic and non flammable even in case of leakage Finally the eff...

Page 7: ...water based synthetic coating with ES2 pigment applied to all areas of the coating surface with no bridging of material between fins Therefore ES2 pigments are suitable for even the most corrosive en...

Page 8: ...unit in case of service parts or warranty questions This nameplate also contains the unit s refrigerant charge and electrical ratings The evaporator nameplate is under the insulation and contains the...

Page 9: ...h The foundation must be strong enough to support the weight of the unit see Dimension and Weight Packaged Unit on page 15 The addition of neoprene pads customer supplied under the unit allows water t...

Page 10: ...can be supplied and installed in the field Piping for units with brazed plate evaporators should have a drain and vent connection at the bottom of the bottom connection piping and at the top of the to...

Page 11: ...iately after unit start up NOTE Failure to comply with these measures may result in performance and reliability problems P Vibration Eliminators Isolation Valves Thermometer Thermowell Thermowell Ther...

Page 12: ...controlled by the chiller s microprocessor The controller will activate the pump whenever at least one chiller circuit is enabled for operation This helps ensure proper start up sequence of the unit...

Page 13: ...y may freeze and not indicate a no flow condition HIGH TEMPERATURE OPERATION CLIC STAND ALONE series units for high temperature operation 105 F to 125 F 40 C to 52 C require the addition of the option...

Page 14: ...iom clicsa cf eng www clima flex com 14 Refrigeration Schematics Figure 5 Refrigerant schematics...

Page 15: ...Top View Side View Isometric View Notas 1 25TR Unit Water connections in 6 IN OUT 2101 mm 82 3 4 in 1835 mm 72 1 4 in 784 mm 30 7 8 in 1168 mm 46 in 2215 mm 87 1 4 in 827 mm 32 5 8 in 817 mm 32 1 8 i...

Page 16: ...d pressure drop in clic stand alone unit Refrigerant Charge Pressure Drop REFRIGERANT CHARGE EVAPORATOR PRESSURE DROP FAMILY TR R410A LBS R410A KG GPM PIPE SIZE DP ft WG CLIC 25 1 X 21 1 X 9 5 60 6 34...

Page 17: ...codes including NECA AA 10402012 for installation of aluminum wiring in buildings ANSI Wiring inside the unit is sized in accordance with the NEC Refer to the unit nameplate and unit selection report...

Page 18: ...can cause serious damage to the chiller The procedure required to reconnect generator power to the mains is as follows 1 Set the generator to always run five minutes longer than the unit start timer w...

Page 19: ...8 SHIELED WIRE J3 J9 WHITE WIRE J3 J9 BLACK WIRE NAKED WIRE ON GROUND COMPRESSOR PROTECTOR Located in compressor electrical connection 24vac protector INTERNAL OVERLOAD PROTECTION MC1 MC2 MC3 HPR PHAS...

Page 20: ...S L3 MS L2 MS L1 R 2 C1 5L3 22X NC 31X NC 14X NO 43X NO CAL4 11 CAL4 11 21X NC 32X NC 13X NO 44X NO TF96 MC1 L3 MC1 L2 MC1 L1 Compressor connection EXISTING WIRES DO NOT DISCONECT FAN 1 FAN 2 COMPRESS...

Page 21: ...ATION ONLY IN 2X18 SHIELED WIRE J3 J9 WHITE WIRE J3 J9 BLACK WIRE NAKED WIRE ON GROUND COMPRESSOR PROTECTOR Located in compressor electrical connection 24vac protector INTERNAL OVERLOAD PROTECTION MC1...

Page 22: ...MS L2 MS L1 R 2 C1 5L3 22X NC 31X NC 14X NO 43X NO CAL4 11 CAL4 11 21X NC 32X NC 13X NO 44X NO TF96 MC1 L3 MC1 L2 MC1 L1 Compressor connection EXISTING WIRES DO NOT DISCONECT FAN 1 FAN 2 COMPRESSOR PR...

Page 23: ...anel mounted models or sold separately on DIN rail mounted models CAREL s APPLICA app available on Google Play for the Android operating system makes it easy to configure parameters and commission the...

Page 24: ...chiller on Microchiller On Are there any alarms Is a high pressure alarm present Is a low pressure alarm present Are there alarms for out of range probes Turn on switch ON OFF Hold on start up time Is...

Page 25: ...apacitor approach The capacitor approximation will be calculated for each circuit The equation is as follows Capacitor approximation Capacitor saturated temperature OAT Suction reheating The suction s...

Page 26: ...he operating or pumping state They should not operate when the circuit is in any other state Compressor start up A compressor must start if it receives a start command from the unit capacity control l...

Page 27: ...the bulb to make sure it is properly connected to the suction line If you can move the bulb manually it is not properly secured The bulb must be perfectly insulated to protect it against the effects o...

Page 28: ...imply has a pump configured in this case this alarm goes together with the current pump configuration A15 This alarm usually appears when the water temperature does not drop due to the current cooling...

Page 29: ...the equipment is electrically linked to the pump start which means that when the pump is turned on the fan is turned on however this icon is currently represented on the controller as fan present Whe...

Page 30: ...rm and save the change Press the down key again and the SEtH menu will appear this parameter is used to change the setpoint in HEAT mode only when the units have this option available otherwise it wil...

Page 31: ...OF THE INTERFACE SCREEN OF THE CAREL APPLICATION VIA CELLULAR PHONE The following image shows the interface of the carel application through Bluetooth communication and monitoring of equipment operati...

Page 32: ...ounters 25 1 C007 BOOL R W FALSE C007 Comp 1 circ 2 reset hour counters 26 1 C010 BOOL R W FALSE C010 Comp 2 circ 2 reset hour counters 27 1 C034 BOOL R W FALSE C034 High press switch input logic 0 N...

Page 33: ...FALSE En_SrcRetTempPrb Connected source return temperature probe 90 1 WaitOtherDevCirc1_ SmartOpnExV BOOL R W 0 91 1 LowNoiseActive BOOL R W FALSE Low noise function active 92 1 S073 BOOL R W FALSE S0...

Page 34: ...anual mode steps 100 1 E003 UINT 0 65535 R W 0 STEPS E003 ExV circ 2 manual mode steps 101 2 E004 REAL R W 6 DELTAKELVIN E004 ExV SH set point in cool 103 2 E005 REAL R W 15 E005 ExV SH control Kp in...

Page 35: ...R W 0 S014 Source fan ON OFF circ 2 manual mode 0 AUTO 1 OFF 2 ON 219 1 S015 USINT 0 101 R W 0 PERCENT S015 Source fan inverter circ 2 manual mode 0 AUTO 1 0 2 1 101 100 220 2 S016 REAL R W 5 CELSIUS...

Page 36: ...r pump 1 overload 9 LP pressure switch 10 User pump 2 overload 11 Remote cmd 1 12 Remote cmd 2 13 Source alarm 292 1 Hc07 USINT 0 6 R W 5 Hc07 Digital input 5 con g 0 Not used 1 User ow switch 2 Comp...

Page 37: ...lve on comp starts 353 1 P012 UINT 0 999 R W 3 SECOND P012 Oil equalisation solenoid valve open time 354 1 P013 UINT 0 999 R W 1 MINUTE P013 Oil equalisation solenoid valve min o time 355 1 P014 UINT...

Page 38: ...circ 2 3 User heater step 2 4 User pump 2 5 Source 6 Frost heater 7 4way valve 8 Oil equal valve 748 1 Hc63 USINT 0 8 R W 1 Hc63 Digital output 3 secondary con g 0 Not used 1 Comp 1 circ 2 2 Comp 2 c...

Page 39: ...gue capacity request max value 817 1 U089 USINT 0 2 R W 0 U089 Analogue capacity request input type 0 0 5V 1 0 10V 2 4 20mA 788 1 Hc90 USINT 0 8 R W 0 HC90 Display value selection Large area 789 1 Hc9...

Page 40: ...rce 1 pump maintenance 17 1 A18 BOOL R FALSE Unit Free cooling fault 18 1 A19 BOOL R FALSE Circuit 1 Discharge pressure probe broken or disconnected alarm 19 1 A20 BOOL R FALSE Circuit 1 Condensing te...

Page 41: ...rce 1 pump maintenance 17 1 A18 BOOL R FALSE Unit Free cooling fault 18 1 A19 BOOL R FALSE Circuit 1 Discharge pressure probe broken or disconnected alarm 19 1 A20 BOOL R FALSE Circuit 1 Condensing te...

Page 42: ...1Circ1_DevAlrm Comp 1 circ 1 in alarm condition 93 1 Comp1Circ1_AbleToOn BOOL R FALSE Comp 1 circ 1 enabled to start 94 1 Comp1Circ1_AbleToO BOOL R FALSE Comp 1 circ 1 enabled to stop 95 1 Comp1Circ1_...

Page 43: ...BOOL R FALSE En_SuctTempPrb_Circ1 Connected suction temp probe for circ 1 167 1 UsrHeater2 BOOL R FALSE UsrHeater2 User heater 2 status 168 1 Al_RegulationAlrms BOOL R FALSE Al_RegulationAlrms Control...

Page 44: ...e displayed on the control panel The control panel The power LED is activated when the frequency inverter is supplied with mains voltage Green LED on The control section is running Yellow LED Warning...

Page 45: ...gnal via the digital inputs has higher priority than the Hand on and Auto on control keys QUICK TRANSFER OF PARAMETER SETTINGS Once the configuration of a frequency converter has been completed store...

Page 46: ...p The following parameter groups can be accessed 0 Operation Display 1 Load Motor 3 Reference Ramps 4 Limits Warnings 5 Digital input output 6 Analog input output 7 Controls 8 Communication and option...

Page 47: ...heck for refrigerant leaks Open the unit for hydraulic installation only Do not remove the connection guards until the hydraulic circuit is closed Check for foreign objects in the fan discharge Check...

Page 48: ...quirements and is in automatic mode Check voltage Motor save which is set to supply the correct supply voltage for the unit The percentage of unbalance of the power supply must be calculated with the...

Page 49: ...ence will begin by checking all pre programmed safety points on the unit If all required conditions are correct the unit will be ready to start operations UNIT CONTROL To start operations turn the ON...

Page 50: ...e performed on a regular basis Over long periods of operation the heat exchanger will become fouled impairing efficiency and reducing the units performance Consult your local supplier about cleaning t...

Page 51: ...mended that the unit be turned on 24 hours prior to first start up to begin warming up the compressor crankcase HYDRAULIC MAINTENANCE Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Cleaning of the hy...

Page 52: ...Inspection of fan blades cleaning of fan blades Quarterly Plan x x x x Real Compressor power consumption check to determine refrigerant loss quarterly Plan x x x x x x Real Compressor oil inspection m...

Page 53: ...the solenoid Check wiring Motor electrical problems Check for open shorted or bubbled motor Loose wiring Check all wire connections and tighten all terminal screws Compressor makes noise or vibrates C...

Page 54: ...of regulating condenser temperature Excess oil used If the system has excess oil recover and adjust by observing the sight glass on the compressor Motor overload relays or circuit breakers open Volta...

Page 55: ...e Loose fitting in oil line Correct to bring conditions within allowable limits Compressor staging intervals too short Control band not properly adjusted Check and correct Water temperature sensor fai...

Page 56: ...iom clicsa cf eng www clima flex com...