3.15 Main Menu - Drive Information - Group
15
Parameter group containing frequency converter
information such as operating data, hardware configuration
and software versions.
3.15.1 15-0* Operating Data
15-00 Operating Hours
Range:
Function:
0 h
*
[0 - 2147483647 h] View how many hours the frequency
converter has run. The value is saved
when the frequency converter is
turned off.
15-01 Running Hours
Range:
Function:
0 h
*
[0 - 2147483647 h] View how many hours the motor has
run. Reset the counter in
. The value is
saved when the frequency converter is
turned off.
15-02 kWh Counter
Range:
Function:
0 kWh
*
[0 - 2147483647
kWh]
Registering the power consumption
of the motor as a mean value over
one hour. Reset the counter in
.
15-03 Power Up's
Range:
Function:
0
*
[0 - 2147483647 ] View the number of times the frequency
converter has been powered up.
15-04 Over Temp's
Range:
Function:
0
*
[0 - 65535 ] View the number of frequency converter
temperature faults which have occurred.
15-05 Over Volt's
Range:
Function:
0
*
[0 - 65535 ] View the number of frequency converter
overvoltages which have occurred.
15-06 Reset kWh Counter
Option:
Function:
[0]
*
Do not reset
Select
Do not reset
[0] if no reset of the kWh
counter is desired.
[1]
Reset counter Select
Reset
[1] and press [OK] to reset the
kWh counter to zero (see
).
NOTE
The reset is carried out by pressing [OK].
15-07 Reset Running Hours Counter
Option:
Function:
[0]
*
Do not reset
Select
Do not reset
[0] if no reset of the
Running Hours counter is desired.
[1]
Reset counter Select
Reset counter
[1] and press [OK] to reset
the Running Hours counter (
) and
to zero (see
also
).
15-08 Number of Starts
Range:
Function:
0
*
[0 - 2147483647 ] This is a read out parameter only. The
counter shows the numbers of starts and
stops caused by a normal Start/Stop
command and/or when entering/leaving
sleep mode.
NOTE
This parameter will be reset when resetting
3.15.2 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data
sources (
) at individual rates
). A trigger event (
)
and window (
) are used to start
and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option:
Function:
Select which variables are to be
logged.
[0]
*
None
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference [%]
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor Current
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1622] Torque [%]
[1626] Power Filtered [kW]
[1627] Power Filtered [hp]
[1630] DC Link Voltage
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®