Using the Telnet/SSH/CLI Interface
Eaton Network Card-MS User’s Guide P-164000100—Rev 1
www.eaton.com/powerquality
59
Shutdown Commands
Use shutdown commands to define UPS behavior during a shutdown (see Table 18).
Table 18. Shutdown Commands
getShutdown
Syntax
getShutdown N [option1] [option2] . . .
Options for N = 0 | 1| 2
Options for N=1: iName | RunTimeToEmptyLimit | RemainingCapacityLimit | ShutdownTimerSelected |
ShutdownTimer | ShutdownDuration | RestartLevel
Options for N=2 or 3: iName | ShutdownTimer | RemainingCapacityLimit | ShutdownDuration |
StartupTimer
Example
#> getShutdown 1 ShutdownDuration
setShutdown
Syntax
setShutdown N [option1] [option2] . . .
Options for N = 0 | 1| 2
Options for N=1:
iName = “xx..xx“
RunTimeToEmptyLimit = xx(0 to 99999 in seconds)
RemainingCapacityLimit = xx(0 to100 in seconds)
ShutdownTimerSelected = 0 | 1(0=No, 1=Yes)
ShutdownTimer = xx(0 to 5999940/60 in minutes)
ShutdownDuration = xx(120 to 9999 in seconds)
RestartLevel = xx(0 to 100%)
Options for N=2 or 3:
iName = “xx..xx“
ShutdownTimer = xx(99 to 99999 in seconds)
RemainingCapacityLimit = xx(0 to 100 in seconds)
ShutdownDuration = xx(120 to 9999 in seconds)
StartupTimer = xx(0 to 65535 in seconds)
Example
#> setShutdown 1 ShutdownDuration=120