background image

Technical Manual Cold Storage Controllers TKP / TKC x130 - x140

Page 9

 'Physical' and 'virtual' sensors

1

. Each 'physical' (real) sensor is able to fulfill up to 3 

functions at the same time (see Assignment Page), 

any sensor is able to do the same job. 

Up to 6 control sensors can be assigned the same 

time.  The  warmest  of  them  initiates  the  cooling 

function. 

2

. It is possible to create a 'virtual' sensor to realize 

different kinds of averaging, e.g. multiple sensors in 

a huge room or averaging of inlet and outlet sensor 

in a chest freezer. The 'virtual' sensor resp. value 

(

sensor 7

) follows from the selectable emphasis of 

the sensors which must have an effect on the result 

(

weighting 1-6

, Assignment Page). The functions 

assigned  to  this  'sensors'  (

funct  sens.  7a-c

, As-

signment Page) are the same as the functions for 

the 'physical' sensors. 

Example

: If the 'physical' sensor 1 got the function 

"

con

" (control sensor) and also the 'virtual' sensor, 

then the warmer one initiates refrigeration.

●  Selection of a "virtual sensor":

  -  Assignment of a function by "

funct sens7a-c

"

 

●  Selection of a 'physical' sensor which must have  

  an effect on the result :

  -  Activating of the sensor by assigning a 

    function (e.g. display only sensor)

●  Set weighting for the selected sensor

  (

weighting 1-6

).

The  sum  of  all  emphasis  values  must  be 

100%. 

Example

If sensor 1 and sensor 2 must have an effect on 

the result and you set "

weighting 1

" to "30%" 

and "

weighting 2

" to "60%", then you get the error 

message "

SEL

" (assignment error).

Further causes for the error message "

SEL

"

●  The sum of all emphasis parameters is 100%,  

  but no virtual sensor function is selected

●  All 4 emphasis values are set to '0' and  a  

  'virtual' sensor function is assigned

●  A physical sensor is switched off, but an   

  emphasis value > 0 is selected. 

Example 1, Chest Freezer:

For the detection of the actual value, inlet and outlet 

sensor must be used. Sensor 1 is mounted at the 

suction side (inlet) and must have an 60% influence 

on the result. Sensor 2 is mounted at the outlet and 

must have an 40% influence.

-  set "

weighting 1

" to "60"

-  set "

weighting 2

" to "40"

-  set "

funct sensor 7a

" to "con" (control sensor)

Example 2, huge room, standard application

Sensors 1-3 must measure the rooms temperature, 

an arithmetic average must be calculated, sensor 4 is 

the defrost limitation sensor in the evaporator.

-  set "

weighting 1+2

" to "33" and "

weighting 3

  to "34"

-  set "

funct sensor 7a

" to "con" (control sensor)

-  set "

funct sensor 4a

" to "df1"

Special Function

If an emphasis parameter value is set to 

100% (others to 0), up to 6 functions can 

be assigned to the corresponding physical sensor. 

This may be of interest for applications where 

more than 3 sensor functions are used.

M

L

M

L

cool.

mode

freez..

refrig relay fan relay

refrig relay fan relay

cool.

mode

refrig.

Caution

 Cooling

Control circuits

This controller is able to control up to 4 independent 

cooling circuits, each with an own setpoint.

Cooling

Cooling is controlled by switching the output relay. 

In case of power loss or controller defects the 

contacts must switch in a position which is safe for 

the application. For this reason we are using the 

N/O-contact for refrigeration applications (fail-safe: 

open contacts). For freezing applications we use 

the N/C-contacts (fail-safe: closed contacts).

This  can  be  set  by  parameter 

"cooling  mode" 

(mode page). The point of cut-off is always the 

valid  setpoint.  The  selection  of  this  parameter 

also affects to the switching characteristic of the 

fan relay. 

The refrigeration relay can be disabled via interface 

(see chapter "networking via E-Link").
Low temperature Limitation

Can be used e.g. for refrigerated shelfs with roller 

blinds to limit the temperature at the air outlet du-

ring night operation. When the temperature at the 

alarm sensor falls below the limit set by "

warn low 

limit

" (Setpoint page) cooling will switch off. This 

value is the threshold for the undertemperature 

alarm at the same time. 

The undertemperature limitation cannot 

be switched off and is also active with 

disabled low temperature warning.

Refrigeration delay after power up

The  start  of  refrigeration  after  power-up  resp. 

mains  loss  can  be  delayed  by  parameter  "

re-

frDlyAftMnsOff

" (Setpoint Page). In plants with 

many cold storages this function prevents that 

after  power-up  all  solenoid  valves  open  at  the 

same  time,  even  though  not  enough  machine 

power is present yet. 

freezing

relay ON

cooling =

relay OFF

warm

cold

setpoint

Hysteresis

cooling = relay ON

cold

warm

setpoint

hysteresis

relay OFF

refrigeration

notice

 Heating function

For one relay it is possible to assign the function 

of heating circuit 1. The setpoint is the cut-off of 

heating and cooling at the same time: 

• 

for cooling at se hysteresis  

and

•  for heating at setpoint - hysteresis.

refrig. ON

heating ON

cold

warm

OFF

setpoint

hysteresis

hysteresis

 Runtime Monitoring

The controller monitors the total running hours per 

day of the cooling outputs. This values are  displayed 

under parameters „

run time refr. x

“ for each circuit. 

One  day  counts  from  the  time  of  the  parameter 

runtime mess at

“ (mode page) until the same time 

of the next day.

Example:

"

runtime mess at

" set to 11:00.

Monitoring time range is from 11:00 o'clock day 1up 

to 10:59 o'clock day 2.
The total runtime of the cooling relays over a day 

will  be  stored  and  displayed  (

"runtime  refr.  1-4"

Actual Values). 

A parameter „

cooling limit

“ can be set to a reasonable 

value (hours per day) which, when exceeded on 

three days in a sequence, will cause an alarm at 

the hour programmed by „

runtime mess at

“. Then 

the alarm relay will be de-activated and the alarm 

LED goes on.

This  alarm  will  be  cancelled  automatically  1 

hour later. 

 Operation with a single compressor

If a single compressor is controlled by a refrigeration 

relay, it is suggestive to have an idle time to prevent 

the machine from damages caused by short cycle 

operation. The compressor can restart only after the 

timer "

compr. pause

" (setpoint page) is run down. The 

remaining time up to the compressors restart can be 

read at "

rem.compr pause X

" (actual page).

If a compressor must be controlled directly, 

never use the cooling mode 'freezing' to 

prevent  compressor  damages  by  conti-

nuous running!

 Second setpoint (night operation)

For each of the 4 circuits a second setpoint is avai-

lable (

2nd setp Ch X

). This can be used for night 

operation  or  other  energy  savings.  The  toggling 

between these setpoints can be made by the internal 

clock or by a digital input. The setpoint which is in 

use at the moment is marked by two arrows like:  

„—> -20,0°C <—“. In the actual values page you 

see also if day or night setpoint is in use.

Internal toggling

  The parameters „

night setpt ON

“ (mode page)  

  and „

night setpt OFF

“ determine the period  

  when the 2nd setpoint will be active. If the  

  function 'night settings' is assigned to one of the  

  digital inputs, it must be connected to mains  

  phase. If the internal timer is not used, set  

  '

night setp. ON

' and 

'night setp. OFF

' times to  

  „OFF“. 
  External toggling

  If the 'night settings' input is open, the 2nd  

  setpoint is activated all time and the internal  

  timer is disabled. With this digital input to mains  

  phase, the normal (1st) setpoint is activated 

  and internal timer is enabled.

 Second Set of Setpoints

The controller offers two sets (layers) of setpoints, 

where the first layer of setpoint is used during normal 

operation and the alternative layer of setpoints with 

other temperatures is used e.g. for other products 

which will be stored only sometimes. For each layer 

there  are  parameters  for  the  setpoints,  the  night 

setpoints,  warning  offsets  and  low  temperature 

warning. The names of the second set parameters 

begin with '

alt

....'.

Toggling between the setpoint layers
1. internal:  with parameter „

setpoint layer

2. external:  assign function „setpoint layer“ to  

   

a digital input. If connected to mains  

   

phase, the 2nd layer is in use.

Summary of Contents for TKC 19130

Page 1: ... defrost act fail page 20 02 18 11 492 actual values 20 02 18 11 49 setpoint page 20 02 18 11 49 defrost page 20 02 18 11 49 mode page 20 02 18 11 49 assignment page 20 02 18 11 49 hist fail page 20 02 18 11 49 ESC RET RET RET RET RET RET RET current failure etc last failure 1 etc sensor 1 etc setpoint level X etc defrost mode etc configuration TKP TKC Test 20 02 18 11 49 RET User Code date time e...

Page 2: ...ge caused by failure to comply with these operating instructions Nor will ELREHA be held liable for any personal injury or damage to property caused by improper handling or failure to observe the safety instructions and recommendations contained in this or any other ELREHA supplied document related to this product Thismanualcontainsadditionalsafetyinstructionsthroughout the functional description ...

Page 3: ...tethe StandardDisplay aftersomeseconds incaseofafailureitwilldisplaytheactualfailure factory set is the actual value of probe 1 This will also displayed if you have selected any parameterandyouhaven ttouchabuttonformore than 3 minutes If you think that it is suggestive to show any sensor value as permanent parameter do the following Change permanent parameter Select the parameter you want to have ...

Page 4: ...2 h m s resettable only 00 00 00 up to runtime relay 6 2 00 00 00 analog value X 1 output is X of the selected range OC1 OC2 OC3 OC4 X 1 voltage at this digital inputs relay status X 1 state of relays 1 6 1 ON avtivated 0 OFF de activated Setpoint Page Level Range Factory setting setpoint layer 1 1 2 1 setpoint Ch 1 1 50 50 C 20 C setpoint Ch 2 1 50 50 C 20 C setpoint Ch 3 1 50 50 C 20 C setpoint ...

Page 5: ...0 60 00 mm ss 15 00 mm ss frame pulse day 2 0 100 100 frame pulse nigt 2 0 100 100 frame pulse act X display of the actual frame pulse duration evtl shifted by the VPR system alm temp low 2 yes no yes night setp ON 2 0 00 thru 23 59 off off night setp OFF 2 0 00 thru 23 59 off off runtime mess at 2 0 23 h off 6 h corr sensor 1 2 calibration offset adjustable 10 actual value also adjustable K 0 up ...

Page 6: ...ly sens funct sensor 1b 3 dto alarm sensor 1 funct sensor 1c 3 dto weighting 1 3 0 100 weighting for the virtual sensor 0 funct sensor 2a 3 dto defr sens 1 1 funct sensor 2b 3 dto funct sensor 2c 3 dto weighting 2 3 0 100 weighting for the virtual sensor 0 funct sensor 3a 3 dto control sens 2 funct sensor 3b 3 dto alarm sensor 2 funct sensor 3c 3 dto weighting 3 3 0 100 weighting for the virtual s...

Page 7: ... OC3 OC4 8 31 95 3 74 89 5 3 52 3 4 E LR E H A RET 2 1 ESC 7 8 6 5 95 3 74 133 5 24 32 30 10 12 14 16 18 20 22 24 26 28 2 4 6 8 z d d z 32 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Analog PCB Supply PCB 129 5 08 ELREHA 4 1 3 2 1 3 2 ESC RET 70 8 2 76 TKC 19 RS 485 4 L 3 2 1 N 7 6 5 TKP 31xx 11 10 9 8 14 13 12 inter com 35 34 33 AC DC 42 41 40 39 38 37 36 RS 485 OUT DO NDO RS 232 DO IN GND 18 15 17 ...

Page 8: ...unit changes to the Customer Level if no key is pressed for about 3 minutes Parameter Protection Identificaton Almost all parameters except the temperature setpoints are protected by a simple password If you have to change a parameter and you have pressed the RET key this display appears The controller expects now the input of a code no This code no Code 1 is related from the actual time of the da...

Page 9: ... will switch off This value is the threshold for the undertemperature alarm at the same time Theundertemperaturelimitationcannot be switched off and is also active with disabled low temperature warning Refrigeration delay after power up The start of refrigeration after power up resp mains loss can be delayed by parameter re frDlyAftMnsOff Setpoint Page In plants with many cold storages this functi...

Page 10: ... Circuit Off Each digital input can be configured to switch off one oremorecoolingcircuits circuitOFFX Ifactivated all regulation and control functions and temperature alarmsoftheconcernedcircuitsaredisabled Never thelesstheothersarestillworking Thisismemorized in the list of the historical failures Relay function unit on The function unit on assigned to an output relay has the effect that this re...

Page 11: ...milar act img 0 10V The outputs provide an image of the value of refrig sensor 1 voltage 50 C 0V 100 C 10V current 50 C 0mA 100 C 20mA act img 4 20mA The outputs provide an image of the value of refrig sensor 1 voltage 50 C 2V 100 C 10V current 50 C 4mA 100 C 20mA Control with the analog output signal PI con trol PID T1 0 10V This PID controller with 0 10V DC signal is assigned to cooling circuit ...

Page 12: ...the temperature in the evaporator reaches the limitation setpoint In case of bad working conditions like to many ice or a defect defrost heater defrost is ter minated by max defr time If the number of defrost periods terminated by timer exceeds the number programmed by parameter n o def evnt alm a failure will be indicated In case of defrost by airflow without evapo rator sensor this function has ...

Page 13: ...detected these times will be ignored On the other hand once icing detected the controller will wait for the next defrost time before starting defrost External command Assign one of the digital inputs to manual defrost By applying voltage to that input it is possible to start defrosting at every moment Defrost heater After the end of the Fan OFF Delay the defrost heater switches on up to the temper...

Page 14: ...s voltage fan operation is set to permanent defrost type is set to on and pause aft defr is set to 0 2 fan in interval mode defrost by fan In use for cold storage chambers with higher temperatures Use a relay output for the fan In this case you select fan operation inter val and defrost type on 3 fan in interval mode defrost by electric heater hot gaz In use for cold storage chambers with lower te...

Page 15: ...he information about the market temperatureandtheairhumidityisdeliveredfrom a host system VPR 52xx to allow the controller to calculate the absolute humidity Limits Temperature 19 24 C Humidity 40 70 r H At the upper limits the frequency ratio is equiva lent to the values set by frame period and frame pulse at the lower limit the pulse width will be reduced by half frame period frame pulse ON OFF ...

Page 16: ...problem is solved To see if this function is released look at solenoid valve actual values page Data transmission disturbances If the controller gets no new information from the VPR it continues working with the actual settings If there was an order from the VPR to close the solenoidvalvesandatechnicaldefectinteruptsthe datatransmissionformorethan30minutes theTKx ignores this order and starts work...

Page 17: ... this purpose If the evapo rator has not such a tube assemble it between the fins in the upper part and assure a good thermal exchange It should be placed at the position where the icing stays the longest time while defrosting This depends of type and manufactureroftheevaporator souse your experience Makesurethatthesensordoesn ttouch the heater or any piping with hot gas defrost it must have some ...

Page 18: ...d for the conformity testing to meet the requirements of EMC and Low Voltage Guidelines EN 55011 2016 A1 2017 EN 61010 1 2010 EN 61326 1 2013 CE marking of year 2018 This statement is made for the manufacturer importer by ELREHA Elektronische Regelungen GmbH Werner Roemer Technical Director D 68766 Hockenheim www elreha de Hockenheim 2018 05 24 Name Address City Date Signature EC Declaration of Co...

Reviews: