51.0077.0004.01 Rev.03 

 

FP wMBusConf - Operating Manual

 

8  M-bus telegrams for registered meters 

Operating Manual 

3

 

M-bus telegrams for registered meters 

 

 

The wMBus adapter simulates all meters registered in the while list. They can either be selected and 
read out using their primary address (if assigned using the RelAirConf parameter setting software) or 

their secondary address. The wMBus adapter always keeps the last wM-bus telegram received from 
the registered meters to hand. If required, the telegram is decrypted and packed in a telegram that 
conforms to M-bus.  

 

Example (addressing directly via primary address 

0x05

): 

REQ_UD2:  

10 7B 05 80 16

 

Note:  
If you wish to use primary addressing, you must use the RelAirConf to program a unique address for 
each sender. 

 

Example (addressing via secondary address 

00h 11h 22h 33h ACh 48h B8h 07h

): 

Selection: 

68 0B 0B 68 53 FD 52 00 11 22 33 AC 48 B8 07 BB 16

 

REQ_UD2:  

10 7B FD 78 16

 

Note:  

The secondary address is transferred directly from the wireless M-bus telegram that is received. 
There are a total of 4 response telegrams that are described on the following pages: 

a)

 

Blank telegram 
If no telegram has yet been received from the registered meter after registration in the white 
list, the device returns a telegram without data records. The data records with RSSI (DR1) and 

age (DR2) are optional and are only transmitted if these options are activated in the wMBus 
adapter (possible as of firmware V1.5.0). 

 

  

RSP_UD: M-bus blank telegram 

Example 

La

ye

Byte no.  Name 

Contents 

Bytes [hex] 

Start 

Start byte 

68h 

Da

ta

 Lin

La

ye

r (D

LL)

 

L-field 

Telegram length  

17h 

L-field 

Telegram length  

17h 

Start 

Start byte 

68h 

C-field 

SND_UD 

08h 

A-field 

Primary address (meter) 

00h 

CI-field 

72h (long header) 

72h 

Tr

an

sp

ort

 L

ay

er (

TP

L)

 

ID-field 

LSB identification number  

00h 

ID-field 

Identification number 

11h 

10 

ID-field 

Identification number (meter ID) 

22h 

11 

ID-field 

MSB identification number  

33h 

12 

Manuf. 

LSB manufacturer code (code = REL) 

ACh 

13 

Manuf. 

MSB manufacturer code 

48h 

14 

Version 

Version  

B8h 

15 

Type 

Device type  

07h 

16 

Acc 

Access number 

01h 

17 

Status 

M-bus status (e.g. error, alarm) 

00h 

18 

Config. 

Configuration field (e.g. encryption) 

00h 

Summary of Contents for wMBus

Page 1: ...Wireless M bus Adapter Wireless M bus to wired M bus Gateway from FP InovoLabs Operating Manual ...

Page 2: ...nual is protected by copyright Any further dissemination is only permitted with permission from the issuer This also applies to copies microfilms translations and storing and processing in electronic systems Trade and brand names used in this manual are registered trademarks of the applicable companies even if they are not designated as such explicitly ...

Page 3: ...sembly and cabling 6 2 2 Setting parameters and starting up 7 3 M BUS TELEGRAMS FOR REGISTERED METERS 8 4 APPENDIX 12 4 1 General technical data 12 4 2 Housing 12 4 3 Power supply 12 4 4 Wireless M bus interface 12 4 5 Wired M bus interface 13 4 6 USB stick supplied as standard 13 4 7 Bibliography 13 4 8 Illustrations 13 4 9 Version information 14 4 10 EU Declaration of Conformity 15 ...

Page 4: ...r software or a failure to observe the warnings in this manual can cause serious personal injury or damage to property In this case no liability is accepted and all warranty claims become invalid Safety relevant regulations When project planning installing starting up maintaining and testing the devices the safety and accident prevention regulations applicable for the specific application must be ...

Page 5: ...mode S1 T1 or C1 The data can be received and decoded unencrypted or AES encrypted according to mode 5 or 7 Figure 2 Wireless M bus system with wMBus adapter and FP S ENGuard IoT gateway Thanks to the configurable white list several wMBus adapters can also be operated in an M bus network Furthermore the wMBus adapter can also be used as a fully fledged wireless M bus master thanks to the mini USB ...

Page 6: ... this purpose The following drawings show the dimensions and the required dimensions for wall installation Figure 3 wMBus adapter dimensions In order to wire the wMBus adapter use a suitable flat head screwdriver to open the cover s housing screws There are three connections on the printed circuit board inside Figure 4 wMBus adapter connections 1 Two screw terminals to connect a wired M bus master...

Page 7: ...s on the circuit board ATTENTION Ensure that the cables are not laid at the top left close to the antenna as this could have a negative effect on the radio signals Tension is relieved by looping the cable ties provided around the cable Once you have completed all assembly and parameter setting work secure the device with an adhesive seal on the housing cover s screws to protect against manipulatio...

Page 8: ...reless M bus telegram that is received There are a total of 4 response telegrams that are described on the following pages a Blank telegram If no telegram has yet been received from the registered meter after registration in the white list the device returns a telegram without data records The data records with RSSI DR1 and age DR2 are optional and are only transmitted if these options are activat...

Page 9: ...d in the wMBus adapter possible as of firmware V1 5 0 RSP_UD Example Layer Byte no Name Contents Bytes hex 1 Start Start byte 68h Data Link Layer DLL 2 L field Telegram length h 3 L field Telegram length h 4 Start Start byte 68h 5 C field SND_UD 08h 6 A field Primary address meter 00h 7 CI field 72h long header 72h Transport Layer TPL 8 ID field LSB identification number 00h 9 ID field Identificat...

Page 10: ... of firmware V1 5 0 RSP_UD Example Layer Byte no Name Contents Bytes hex 1 Start Start byte 68h Data Link Layer DLL 2 L field Telegram length from the C field checksum 1Dh 3 L field Telegram length from the C field checksum 1Dh 4 Start Start byte 68h 5 C field SND_UD 08h 6 A field Primary address meter 00h 7 CI field 72h long header 72h Transport Layer TPL 8 ID field LSB identification number 00h ...

Page 11: ...dapter therefore sends an application error RSP_UD Example Layer Byte no Name Contents Bytes hex 1 Start Start byte 68h Data Link Layer DLL 2 L field Telegram length from the C field checksum 10h 3 L field Telegram length from the C field checksum 10h 4 Start Start byte 68h 5 C field RSP_UD 08h 6 A field Primary address meter 00h 7 CI field Application error from the device long 6Fh Transport Laye...

Page 12: ...olystyrene light grey W x L x H 93 93 x 55 mm 3 66 3 66 2 17 Protection class IP54 IP65 possible if the cable is fed through carefully Antenna Internal 4 3 Power supply With an M bus connection Supply from M bus with max 5 standard loads current 7 5 mA With a USB connection Supply from the USB current 90 mA 4 4 Wireless M bus interface Standard EN13757 4 and EN13757 3 OMS compatible Reception mode...

Page 13: ...ual Documentation FP wMBusConf operating manual_Rev1 0 pdf wMBusConf software 4 7 Bibliography 1 FP S OTGuard Hardware Manual 510071900601_XX_FP_S OTGuard_HW Manual_EN pdf 2 FP TiXML Reference EN 510058920001_XX_FP TiXML Reference_EN pdf 3 FP PLC TiXML Manual 510058920101_XX_FP PLC TiXML Manual_EN pdf 4 FP SCADA GLT Manual 510058920601_XX_FP SCADA GLT_EN pdf 5 FP OpenVPN Toolkit Quick Guide 510058...

Page 14: ...f Operating Manual 14 Appendix Operating Manual 4 9 Version information Version Date Author Changes Person responsible 03 23 02 2021 First English Issue IVH 02 27 10 2020 Code number layout Ortmann 01 16 12 2019 Henze First issue Henze ...

Page 15: ...51 0077 0004 01 Rev 03 FP wMBusConf Operating Manual 15 Operating Manual Appendix 4 10 EU Declaration of Conformity ...

Reviews: