PROGRAMMING PARAMETERS

(1) When sensor type is changed, Up.L, Lo.L, H.Set, A.Set, H.hys,

Error Messages:

A.hys, r.Alr, b.Alr, oFFs may be set to a new value automatically,

Fail:

 Sensor failure or sensor selection wrong

according to the selected sensor.

E.FLS:

 Hardware failure

(2) ON-OFF control is the only option for Cooling function 

E.CAL:

 Hardware failure

(3) If sensor type is selected as Pt.0, J.0, K.0 or t.0.

E.EPr:

 Memory failure

Gürbüzo

ğ

lu Elektronik San. ve Tic. Ltd. 

Ş

ti.

http://www.gemo.com.tr.

Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye

e-posta: info@gemo.com.tr

Tel: +90-312-3503900, Fax: +90-312-3511117

3

SET

H.hys /

C.hys

0 .. 50 / 

0.0 .. 50.0 (3)

o

C

SET

Heat/Cool Hysteresis (

o

C):

PID is active if set to 0
(for H.Hys) (

o

C)

A.hys

SET

Pb.C

5 .. 150 

o

C

SET

Ct

1 .. 200 sec

SET

oFFS

SET

td

SET

+

CodE

Enter 162

SET

UP.L

Lo.L ..

Upper Scale (

o

C) 

SET

Upper limit value for Lo.L,
H.SET and A.SET. Upper Scale value
differs according to the selected
sensor type.

AL.tY

SET

r.ALr/
b.ALr

SET

ti

0:00 .. 30:00

min:sec

SET

AL.tY=

 Abs,-Abs,

SnS.O,

SnS.F

Inpt

Sensor Type (1)

SET

J, J.0: J type T/C
K, K.0: K type T/C
t, t.0: T type T/C
S: S type T/C
r: R type T/C
Pt, Pt.0: Pt100

h-C

Select

function (2)

SET

HeAt: heating function
Cool: cooling function

Lo.L

Lower Scale ..

UP.L (

o

C) 

SET

Lower limit value for UP.L,
H.SET and A.SET. Lower Scale value
differs according to the selected
sensor type.

P.Err

% 0 .. 100

SET

Determines the duty cycle of OUT output
when “Fail” message is displayed. If 0, OUT is always
OFF. If 100, OUT is always ON, when device “fails”.
Period is Ct.

H.Hys
not  0

Back

Press “Back”

to return to the 

top of  

parameters 

programming 

block

Integral Time:
In min:sec If set to 0:00,
P, PD is active (integral OFF).

Derivative Time:
In min:sec. If set to 0:00,
P, PI is active (derivative OFF).

Alarm Hysteresis (

o

C)

Proportional Band in (

o

C)

Control period (sec)

Offset Value; Offset is directly added
to the measured value. This feature shall
be used for user calibration. Normally set to 0.

Enter 162 to pass
to parameter prog. mode

Relative or band Alarm
Value. Displayed if AL.ty is
other then Abs or –Abs. 

Press for 2 sec.

Upper Display

C.dLY

0 .. 300 sec

SET

Active only in cooling mode.
Minimum delay before OUT
becomes ON after it becomes OFF. 

Abs,rel,bnd,bn.i

-Abs,-rel,

-bnd,-bn.i,

SnS.O, SnS.F 

Alarm Type:
Abs: Absolute         -Abs: Absoloute, invert out   SnS.O: Sensor failure 
rel: Relative             -rel: Relative, invert out         Continuous out
bnd: band                -bnd: band, invert out            SnS.F: Sensor failure
bn.i: band inhibit     -bn.i: band, invert out            Flashing out

h-C=

heat

CodE

Enter “262”

to start

auto-tune

SET

Upper Display

“tunE”

flashes

 Before starting Auto-tune, adjust H.SET.

 Auto-tune does not start in “cooling” mode.

 Process value may exceed H.Set during auto-tuning.

 After auto-tuning, control form automatically switches
 to PID mode.

 Auto-tuning is stopped (interrupted) any time by 
 pressing any key. In this case, the parameters before 
 auto-tuning is valid.

 Auto-tuning may not always determine the best values
 for your process.

Factory SET Values:
H.SEt: 100 

o

C

A.SEt: 400 

o

C

Inpt : J
H-C : Heat
H.hys: 0 

o

C

A.hys: 3 

o

C

Pb.C: 30 

o

C

Ct: 4 sec
ti: 5:00 min:sec
td: 1:00 min:sec
UP.L: 400 

o

C

Lo.L: 0 

o

C

oFFS: 0 

o

C

AL.tY : rel
r.ALr: 3 

o

C

C.dLY: 15 sec
P.Err: 0
C-t: 0.0 

o

C / min

L.dSP: yes
o.Sht: oFF
SECU: AH

1 .. 50 / 

0.1 .. 50.0 (3)

o

C

0:00 .. 10:00

min:sec

-100 .. 100 / 

-100.0 .. 100.0 (3)

O

C

-100 .. 100 / 

-100.0 .. 100.0 (3)

O

C-t

0.0 .. 300.0

o

C / min

SET

If C-t is not 0, ramping starts after power on. SET value
is incremented or decremented C-t degrees per minute
until SET reaches H.SEt or C.SEt.

CodE

Enter “555”

for factory

reset

SET

“YES” / “nO”

 To return to factory settings:
 Code > 555 > select “yes” > 
 Press “SET” 

Upper Display

yes: Lower display ON
no: Lower display OFF

SET

L.dSP

yes .. no

End Prog.

o.Sht

OFF, 10.0,

5.0, 3.0,

1.0, 0.2

SET

SECU

AH, -H, A-, --

SET

AH: ALARM SET and HEAT SET may be SET,
-H : Only HEAT SET may be SET,
-A : Only ALARM SET may be SET,
-- : ALARM SET and HEAT SET may not be SET.

Over shoot reduction: All options other than “OFF” may help  to reduce over 
shoot more but also may increase instability around SET point. For this reason;
First try “OFF” option then 10.0->5.0->3.0->1.0->0.2 options if needed.
Options 1.0 and 0.2 are most sensitive and may result more instability around 
SET point among other options. With this parameter, over shoot is not allowed
more than; OFF: not limited, 10.0: 10 , 5.0: 5 , 3.0: 3 , 1.0: 1 , 0.2: 0.2 degrees 
(over SET point).

H.Hys

not  0

AL.tY

SnS.O

or

SnS.F