Model IR4000M
11
Register
Address
(Hex)
Parameter
Function
Data
Type
Data Range
Access
0023h
Starting Register
Address errors for
CH2
Number of CH2
Starting Register
Address errors.
Numeric
Value
0-65535 decimal
R
0024h
Reserved
N/A N/A
N/A
N/A
0025h
CRC errors HI for
CH2
Number of CH2 CRC
HI errors
Numeric
Value
0-65535 decimal
R
0026h
CRC errors LO for
CH2
Number of CH2 CRC
LO errors
Numeric
Value
0-65535 decimal
R
0027h
Overrun errors
for CH2
Number of Overrun
errors for CH2
Numeric
Value
0-65535 decimal
N/A
0028h
Framing errors for
CH2
Number of framing
errors for CH2
Numeric
Value
0-65535 decimal
R
0029h
Parity errors for
CH2
Number of Parity
errors for CH2
Numeric
Value
0-65535 decimal
R
002Ah
Reserved
N/A
N/A
N/A
N/A
002Bh
Reserved
N/A
N/A
N/A
N/A
002Ch
Clear Comm
errors for CH1
Clears CH1
communication errors
Numeric
Value
See parameter
description
W
002Dh
Clear Comm
errors for CH2
Clears CH2
communication errors
Numeric
Value
See parameter
description
W
002Eh
Reserved
N/A N/A
N/A
N/A
002Fh
Reset Events
Clears events of
resets event flag
Numeric
Value
0 - Clear Events,
1 - Resets Event
Happened flag
W
0030h
Run Time hi
High word of Run
Time in Seconds
Numeric
Value
0-65535 decimal
R/W
0031h
Run Time low
Low word of Run
Time in Seconds
Numeric
Value
0-65535 decimal
R/W
0032h
Real Time Clock
Year, Month
Read/Set year and
month of RTC
Numeric
Value
1 –99 year, 1–
12 month
R/W
0033h
Real Time Clock
Day, Hour
Read/Set day and
hour of RTC
Numeric
Value
1 – 31 day,
0 – 23 hour
R/W
0034h
Real Time Clock
Minute, Second
Read/Set minutes
and seconds of
RTC
Numeric
Value
0 – 59 minutes
0 – 59 seconds
R/W
0035h
Power Cycled
Flag
Time Reset After
power Cycled
Numeric
Value
0 = Time not
Reset, 1 =
Time Reset
R
0036h
Event Index
Index of Logged
Events
Numeric
Value
0 - 9
R/W
0037h
Running Time
Hi
Running Time Hi
for Warning Event
log entries
Numeric
Value
0 - 65535
R