9.2 Basic communication command
In this section, we will show you some basic communication commands that will help you debug or
regulate the UPS system.
9.2.1 QGS
QGS means to request general status parameters of the system. The command format is:
Computer
:
QGS<cr>
UPS: (MMM.M HH.H LLL.L NN.N QQQ.Q DDD KKK.K VVV.V SSS.S XXX.X TTT.T
b9b8b7b6b5b4b3b2b1b0a0a1<cr>
Data
Description
Notes
a
(
Start byte
b
MMM.M
Input voltage
M is an Integer number 0 to 9. The units is V.
c
HH.H
Input frequency
H is an Integer number 0 to 9. The units is Hz.
d
LLL.L
Output voltage
L is an Integer number 0 to 9. The units is V.
e
NN.N
Output frequency
N is an Integer number from 0 to 9. The units is Hz.
g
QQQ.Q
Output current
Q is an Integer number from 0 to 9. The units is A.
h
DDD
Output load percent
For Off-line UPS: DDD is a percent of maximum VA,
not an absolute value.
For On-line UPS: DDD is Maximum of W% or VA%.
VA% is a percent of maximum VA.
W% is a percent of maximum real power.
j
KKK.K
Positive BUS voltage
K is an Integer ranging from 0 to 9. The units is V.
k
VVV.V
Negative BUS voltage
V is an Integer ranging from 0 to 9. The units is V.
l
SSS.S
P Battery voltage
S is an Integer ranging from 0 to 9. The units is V.
m
XXX.X
N Battery voltage
X is an Integer ranging from 0 to 9. The units is V.
n
TTT.T
Max Temperature of the
detecting pointers
T is an integer ranging from 0 to 9. The units is °C
o
b9b8b7b6
b5b4b3b2
b1b0
a0a1
Ups status
B9,b8:
00: standy;
01: line-interactive;
10: on-line.
B7: Utility Fail
b6: Battery Low
b5: Bypass/Boost Active
b4: UPS Failed
b3: EPO
b2: Test in Progress
b1: Shutdown Active
b0: bat silence
a0: Bat test fail
a1: Bat test OK
Example: