25
PME
−
MP55IBS
HBM
A0822-2.1 de/en
The parameter set number is coded in 2 bit binary:
Bit 8 Bit 9
Parameter set no.
0
0
1
1
0
2
0
1
3
1
1
4
Status 2
Double status word 2 returns detailed error flagging.
Bits
Name
Meaning
0
HardwOvfl
Hardware overflow
1
ADCOvfl
ADC overflow
2
GrossOvfl
Gross signal overflow
3
Net-Ovf
Net signal overflow
4
AOutOvfl
Analogue output overflow
5
MaxOvfl
Maximum overflow
6
MinOvfl
Minimum overflow
7
NegOvfl
Overflow in negative direction
8
LVS1
Status of limit value switch 1
9
LVS2
Status of limit value switch 2
10
LVS3
Status of limit value switch 3
11
LVS4
Status of limit value switch 4
12
SkalInError
Scaling input invalid
13
SkalOutError
Scaling output invalid
14
GainError
Nominal value exceeded
15
Init.Error
Works calibration defective
16
TransducerError
Transducer error
21
Stand Still
Standstill recognition
22..31
Res
Reserved
Tab 4.2
Contents of status 2
4.2.2 Outputs (from the PLC to MP55IBS)
Limit values
Limit values are displayed in the same format as the measured values (16 bit
integer, 32 bit integer or floating format). The operating direction and
hysteresis remain unchanged and are set via the operating panel or the CAN
bus.