Appendix A: EtherNet/IP Implementation
21 (26)
A
EtherNet/IP Implementation
See also the
Netbiter Argos documentation
on how to configure EtherNet/IP.
A.1
Client
Connection Type
UCMM (Class 1 and 3 connection not supported)
Adapter Timeout
1000 ms
Services
The following services are implemented:
Code
Service Name
Addressing
Note
0x0E
Get_Attribute_Single
Class, Instance,
Attribute
0x10
Set_Attribute_Single
Class, Instance,
Attribute
0x4C
Read_Tag_Service
Symbolic Segment
Addressing
Can be used to access Controller Tags.
Vendor specific service code (see note below).
0x4D
Write_Tag_Service
Read_Tag_Service and Write_Tag_Service using symbolic segment addressing is only sup-
ported by some PLCs. Please refer to the PLC vendor’s documentation for more information.
A.2
Adapter
A.2.1
Identity Object (0x01)
Class Attributes
No attributes are implemented.
Instances
Instance 1 is implemented with the following attributes:
ID
Access
Name
Value
1
Get
Vendor ID
90
2
Get
Device Type
100
3
Get
Product Code
85
4
Get
Revision
1
5
Get
Status
1
6
Get
Serial Number
...
7
Get
Product Name
Netbiter
Services
The following services are implemented:
Code
Class
Instance
Service Name
0x01
No
Yes
Get_Attribute_All
0x0E
No
Yes
Get_Attribute_Single
Netbiter EC300 Series User Manual
SCM-1202-012
2.2