Page 16 of 28
Quick Start Guide Stabiliti™ Series PCS
MAN-00114, Rev D
109
p1_v_ab_rms
int16
RO
AC1 A-B RMS voltage
110
p1_v_bc_rms
int16
RO
AC1 B-C RMS voltage
111
p1_v_ca_rms
int16
RO
AC1 C-A RMS voltage
115
p1_i_a_ext_adc
int16
RO
AC1 phase A RMS current
116
p1_i_b_ext_adc
int16
RO
AC1 phase B RMS current
117
p1_i_c_ext_adc
int16
RO
AC1 phase C RMS current
118
p1_power_factor
int16
RO
AC1 power factor
119
p1_real_power
int16
RO
AC1 real power
120
p1_reactive_power
int16
RO
AC1 reactive power
121
p1_apparent_power
int16
RO
AC1 apparent power
Table 2: DC2/DC3 Registers
Addr
Register Name
Format
Factory
Default
Comments
128
/192
p2/p3_port_type
uint16x
R/W
0x0002
DC port
129
/193
p2/3_control_method
uint16x
R/W
0
0x0000 - IDLE
0x0001 - NET
0x0002 - MPPT
0x0301 - DC CURRENT
0x0401 - DC POWER
130
/194
p2/p3_ramp_rate
uint16
R/W
50
IDLE
– not applicable
NET
– not applicable
DC CURRENT
– factory default current
ramp rate = 5 A per second
DC POWER
– factory default power ramp
rate = 500 W per second
131
/195
p2/p3_throttle_port_
setpt
int16x
R/W
0x0000
If p2 or p3_control_method = 0x0001:
throttle port AC1 = 0; throttle port DC3 (or
DC2) = 1
132
/196
p2/p3_current_setpt
int16
R/W
0
If p2/p3_control_method = 0x0301: DC
Current setpoint
133
/197
p2/p3_power_setpt
int16
R/W
0
If p2/p3_control_method = 0x0401: DC
Power setpoint