’Online’ Commands for Parameter Set Operations
Test parameter set
Copy parameter set
Possible acknowledgements
Command
’PA’
Description
Tests the given parameter set for validity using a checksum.
Parameter
’0’ tests the current parameter set.
’1’ tests the customer-specific parameter set (MA 10 only).
Acknowledgement all possible acknowledgements are listed below.
Command
’PC’
Description
Copies the given source parameter set into the given target parameter set
Parameter
Example
BCL 80 Stand alone:
’0’ current parameter set.
’2’ parameter set with factory default settings.
’PC20’: Reset to factory default settings
Parameter
Examples
BCL 80 with MA 10:
’0’ current parameter set.
’1’ customer-specific parameter set.
’2’ parameter set with factory default settings.
’PC20’: Reset to factory default settings
’PC01’: The current parameter set is copied in the customer-specific parameter
set (backup)
’PC10’: Reset to customer-specific settings
Acknowledgement all possible acknowledgements are listed below.
Acknowledgement Description
’PS0’
valid parameter set
’PS1’
invalid message
’PS2’
invalid message length
’PS3’
invalid type of BCC check sum
’PS4’
invalid BCC check sum
’PS5’
invalid length of data
’PS6’
invalid message parameters
’PS7’
invalid start address in parameter set
’PS8’
invalid CRC check sum of parameter set
’PS9’
invalid type of parameter set
Note!
A valid parameter set operation must be acknowledged with ’PS0’. Should an error occur,
the command should be repeated. Repeated error acknowledgements indicate an error in
the parameter set. If in doubt, contact your Leuze sales or service office (see back page for
addresses).