EM58 – HS58 - HM58 MODBUS TCP/IP
position of the encoder in the moment when the
suggest activating the preset value when the encoder is in stop.
Default = 0 (min. = 0, max. = 134217727 *)
for EM58 series
0 (min. = 0, max. = 262143 *)
for HS58 series
0 (min. = 0, max. = 1073741823 *)
for HM58 series
* See the note below.
EXAMPLE
Let's take a look at the following example to better understand the preset
function and the meaning and use of the related registers and commands:
The encoder position which is transmitted results from the following
calculation:
Transmitted value
=
read position
(it does not matter whether the position is
physical or scaled) +
preset setting (
), then the transmitted value and the read position are necessarily
= 0 and
= 0.
command, the system saves the current encoder position in
registers. It follows that the transmitted value and
read position
= 0; in other words, the value set next to the
registers is paired with the current position of the encoder as you wish.
For example, let's assume that the value “50” is set next to the
when the encoder position is “1000”. In other words, you want to receive the
value “50” when the encoder reaches the position “1000”.
We will obtain the following:
Transmitted value
=
read position
(=”1000”) =
50
.
The following transmitted value will be:
Transmitted value
=
read position
(=”1000”) =
51
.
And so on.
NOTE
MAN EM58_HS58_HM58 MT E 1.1.odt
Programming parameters
57 of 104
Summary of Contents for EMC58 MT
Page 101: ...This page intentionally left blank ...
Page 102: ...This page intentionally left blank ...