Communication operation and setting
(6) Modbus registers
System environment variable
∗1
The communication parameter values are not cleared.
∗2
For write, set the data as a control input instruction.
For read, data is read as an inverter operating status.
∗3
For write, set data as the operation mode setting.
For read, data is read as the operation mode status.
Real time monitor
Refer to
page 123 for details of the monitor description
.
∗1
When "0.01 to 9998" is set in
Pr. 37
and "01" in instruction code HFF, the data format is 6 digits (E").
∗2
Input terminal monitor details
∗3
Output terminal monitor details
Register
Definition
Read/write
Remarks
40002
Inverter reset
Write
Any value can be written
40003
Parameter clear
Write
Set H965A as a written value.
40004
All Parameter clear
Write
Set H99AA as a written value.
40006
Parameter clear
Write
Set H5A96 as a written value.
40007
All parameter clear
∗1
Write
Set HAA99 as a written value.
40009
Inverter status/control input instruction
Read/write
See below.
40010
Operation mode/inverter setting
Read/write
See below.
40014
Running frequency (RAM value)
Read/write
According to the
Pr. 37
settings, the frequency
and selectable speed are in 1r/min
increments.
40015
Running frequency (EEPROM value)
Write
b15
b0
—
—
—
—
—
—
—
—
—
RH
RM
RL
—
—
STR
STF
b15
b0
—
—
—
—
—
—
—
—
—
—
ABC
—
—
—
—
RUN
<
Inverter status/control input instruction
>
∗1
The signal within parentheses is the default setting. The description changes depending on the setting of
Pr. 180 to Pr. 182 (input terminal function
selection) (refer to page 108)
.
Each assigned signal is valid or invalid depending on NET.
∗2
The signal within parentheses is the default setting. Definitions change according to the
Pr. 190, Pr. 192 (output terminal function selection) (refer to page114)
.
Bit
Definition
Control input instruction
Inverter status
0
Stop command
RUN (inverter running)
1
Forward rotation command
Forward rotation
2
Reverse rotation command
During reverse rotation
3
RH (high-speed operation
command)
SU (up-to-frequency)
4
RM (middle-speed operation
command)
OL (overload)
5
RL (low-speed operation
command)
0
6
0
FU (frequency detection)
7
RT (second function selection)
ABC (fault)
8
AU (current input selection)
0
9
0
0
10
MRS (output stop)
0
11
0
0
12
0
0
13
0
0
14
0
0
15
0
Fault occurrence
<
Operation mode/inverter setting
>
The restrictions depending on the operation
mode changes according to the computer
link specifications.
Mode
Read Value
Written
Value
EXT
H0000
H0010
PU
H0001
—
EXT
JOG
H0002
—
NET
H0004
H0014
PU+EXT
H0005
—
Register
Description
Unit
40201
Output frequency/speed
0.01Hz/1
40202
Output current
0.01A
40203
Output voltage
0.1V
40205
Output frequency setting/speed
setting
0.01Hz/
0.001
40208
Converter output voltage
0.1V
40209
Regenerative brake duty
0.1%
40210
Electronic thermal relay function
load factor
0.1%
40211
Output current peak value
0.01A
40212
Converter output voltage peak value
0.1V
40214
Output power
0.01kW
40215
Input terminal status
∗2
—
40216
Output terminal status
∗3
—
40220
Cumulative energization time
1h
40223
Actual operation time
1h
40224
Motor load factor
0.1%
40225
Cumulative power
1kWh
40252
PID set point
0.1%
40253
PID measured value
0.1%
40254
PID deviation
0.1%
40261
Motor thermal load factor
0.1%
40262
Inverter thermal load factor
0.1%
40263
Cumulative power 2
0.01kWh
40264
PTC thermistor resistance
0.01k
Ω
Register
Description
Unit