Moog ACV with CANopen bus interface
6 Signal routing and scaling
Drive transducer interface
B99224-DV018-D-211, Rev. A, October 2018
72
6.3 Drive transducer interface
There are seven available transducers interfaces which can be used to convert actual values to be forwarded
to the controller:
• Analog input 0…4, used for pressure, position or other sensors
• Encoder
• SSI
• For special application any parameter can be mapped to an interface e.g. from a field bus.
The logic to select the interface is called transducer interface. The following figure shows how routing and
scaling of the actual value is done for the available inputs.
With the interface type <Type> (0x6202), the type of value conditioning can be selected depending on the
sensor.
Figure 29: Drive actual value path
8. Transducer interface
3...7. Transducer interface
2. Transducer interface
1. Transducer interface
p
Analog input 2
Analog input 3
Analog input 4
Analog input 1
Analog input 0
Internal pressure
transd. in pipe A
p
p
p
p
pA
0x34040010
0x32040010
0x320C0010
0x32140010
0x321C0010
0x32240010
0x...
<TransducerPort>
(0x4032)
<Sign>
(0x6203)
General actual value scaling
<GeneralInputMinimum> (0x6228)
<GeneralInputMaximum> (0x6229)
<GeneralInputOffset> (0x622B)
<GeneralInputMin.Signal> (0x622C)
<GeneralInputMax.Signal> (0x622D)
<InterfaceNumber>
(0x6201)
1
2
3...7
8
All parameters in this box are only
effective for the choosen
transducer interface number
<InterfaceNumber> (0x6201)!
<ActualValue1>
(0x6210)
<ActualValue2>
(0x6211)
<ActualValue3...7>
(0x6212...0x6216)
<ActualValue8>
(0x6217)
Field bus or
Local CAN
Any signed
16 bit / 32 bit
param. from the
object dictionary
p
p
0x...
SSI / incremental /differential
encoder actual value scaling
<PositionResolution> (0x6240)
<PositionOffset> (0x6141)
General actual value scaling
<MinimumReference> (0x6230)
<MaximumReference> (0x6231)
<MinimumInterface> (0x6233)
<MinimumInterface> (0x6234)
<Type> (0x6202)
5 (General)
-3 ( filter )
-2 (16 bit)
-1 (32 bit)
0 (No transducer function)
64, 65, 66 (Encoder)
67 (Analog)
SSI / Incremental
Encoder
s/v
0x56130020
Pressure actual value scaling
<MinimumPressure> (0x6220)
<MaximumPressure> (0x6221)
<PressureArea> (0x6222)
<PressureOffset> (0x6223)
<MinimumSignal> (0x6224)
<MaximumSignal> (0x6225)
2 (Pressure)
Per default, analog input 0 and 1 are used for the analog setpoint values. Therefore the inputs
2…4 are normally used for actual values.
Chapter "6.4 Analog inputs", page 86
Before reading or writing configuration values of a particular transducer interface it is necessary to
select the particular interface by setting the interface number <InterfaceNumber> (0x6201).