Mx350_01a_oi_e.docx / Nov-19
page 34 / 72
Continuation “Counter B Settings“:
SECOND MODE
Setting of the batch counter / total counter.
The function of batch counting according to a preset value is only possible in combination with the switch
condition “automatic reset to zero” (RESULT <= PRES-> 0), “automatic reset to set value” (RESULT>=PRES-
>VALUE) or “set the counter value to the respective preselection value” (RESULT <=0-> SET).
When SECOND MODE is active, PRESELECTION serves as the present value (SOURCE 1-4) for the SECOND
COUNTER B.
Example for the batch counter:
If the batch counter should increment 1 all 1000 pulses, the value e.g. PRESELCTION 1 has to be set to 1000, the
related reference source SOURCE 1 to “COUNTER B”, the corresponding switching condition MODE 1 to
"RESULT>=PRES->0" and SECOND MODE to INCREMENT BATCH. Should an output be turned on after a batch
amount of 33, e.g. PRESELECTION 2 has to be set to 33, the related reference source SOURCE 2 to “SECOND
COUNTER B” and the switching condition of MODE 2 has to be set to display value greater than or equal
(RESUL>=PRES).
Example for the total counter:
For the total counter, SECOND MODE must be set to “TOTAL COUNTER”. The total counter counts here parallel to
the main counter. e.g. If the total counter should automatically reset to 0, when 4000 is reached, the preset value
e.g. PRESELECTION 3 must be set to “4000”, the reference source SOURCE 3 must be set to
“SECOND COUNTER B” and the corresponding switching condition MODE 3 must be set to "RESULT> = PRES-> 0"
0 OFF
No batch counter and no total counter
1 INCREMENT BATCH
increment batch counter
2 DECREMENT BATCH
decrement batch counter
3 USE INPUTS ONLY
increment / decrement batch counter only by external commands
(see command menu)
4 TOTAL COUNTER
Total counter is activated
SECOND SET VALUE
With a "RESET / SET " command (command “SET SECOND B” via control input), the Second Counter B (batch
counter / total counter) is set to this value.
(Parameter only visible with activated "SECOND MODE")
-99999999
Smallest value
0
Default value
+99999999
Highest value
SECOND DECIMAL POINT
This value defines the position of the decimal point.
(Parameter only visible with activated "SECOND MODE")
0 NO
No decimal point
1 0000000.0
Decimal point at the specified position
2 000000.00
Decimal point at the specified position
3 00000.000
Decimal point at the specified position
4 0000.0000
Decimal point at the specified position
5 000.00000
Decimal point at the specified position
6 00.000000
Decimal point at the specified position
7 0.0000000
Decimal point at the specified position