VBA-2E-G11-I/U/PT100-*
Appendix A
Input
Programming Instructions
Number/type
Two analog inputs
Current: 4 mA ... 20 mA/4 mA ... 20 mA
Voltage: 0 V ... 10 V
Pt100: -200
°
C ... 850
°
C
Power supply
From AS-Interface (switch setting INT, basic setting) or from
auxiliary power source U
AUX
(switch setting EXT)
Current rating
140 mA from AS-Interface; overload and short-circuit proof
600 mA from external auxiliary power source U
AUX
, overload
and short-circuit proof
Input resistance
Current input: max. 70
Voltage input: 100 k
Measurement current
For Pt100: approx. 1 mA
Measurement accuracy
Voltage/current: 0.1% of end value
Pt100: 0.1% of temperature displayed [
°
C] + 0.3
°
C
Resolution
16 bit/1
µ
A (current input) or
16 bit/1 mV (voltage input) or
16 bit/0.1
°
C (temperature input)
Temperature effect
Voltage/current: 20 ppm/K
Pt100: (10 ppm of temperature displayed [
°
C] + 0.003
°
C)/K
Profile
S-7.3.D
IO code
7
ID code
3
ID2 code
D
Data bit (function via AS-
Interface)
The data value is transmitted as defined by AS-Interface profile
7.3.
Parameter bit
(programmable via AS-i)
Function
P0
50/60 Hz filter
P0=1, activated
P0=0, deactivated
P1
Programming the second channel
P1=1, channel 2 is programmed
P1=0, channel 2 is not programmed
P2
Notification of peripheral fault in the event of a measuring
overrange
P2=1, peripheral fault is reported
P2=0, peripheral fault is not reported
P3
P3=1, normal operation
P3=0, both channels in current mode and without wire break
detection