background image

12

|  

Systemair NOVA drive 370

7 LED behaviour

The three LEDs in NOVA RHC (red, yellow, green) behaviour is depicted below.

Start/Stop signals

Stopped and ready to start

The inverter indicates it is stopped but ready to start (no faults prevent starting). 
In this case the green LED flash slowly (500ms on, 500 ms off). If the inverter 
has warnings or errors, then it will not show this.

Running

When the inverter is running, the green LED is ON all the time. If the inverter has 
warnings or errors then it will show those instead.

Retrying

When the inverter has been stopped due to a fault and try to start again on its 
own, it flash green fast (200 ms on, 200 ms off). It stops flashing when it has 
reached the setpoint. As the control strategy is V/f, tolerance for reaching the 
setpoint is 0. If the inverter has warnings or errors it will overwrite those and not 
show those warnings and errors until the retry has reached the setpoint.

Faults and warnings

Warnings

When the inverter has a warning it flashes the yellow LED as many times as the 
warning code and then pauses (400 ms on, 400 ms off, 2000 ms pause at the 
end). The action is repeated until the warnings are cleared. If more than one 
warning is activated the latest warning is the one shown.

Faults

When the inverter has an error that prevents it from starting then it flashes red 
as many times as the error code and then pauses (400 ms on, 400 ms off, 2000 
ms pause at the end). The action is repeated until the errors are cleared. If a 
warning appears after an error the inverter will still show the latest error as it 
has higher priority.

Rotary guard

Rotary guard passed

When the rotary guard passes it shows the red-green-red-green sequence 
(200ms each LED). If the inverter has no warnings or faults then this sequence 
will override any LED indication immediately. If there are warnings or faults it will 
wait for the fault sequence to stop toggling the LEDs indicating the error number 
and will show the rotary guard sequence after.

Table 8 – LED behaviour table

8 Fault behaviour

Each error has a maximum number of retries allowed within a 30 minute window. After 30 minutes of no errors the 
counts are reset. Errors are only counted when the motor is running or trying to run. Rotary Guard errors do not get 
auto-reset after 30 minutes and stay forever until the reset fault command is sent. This is because at low speeds it can 
take more than 30 minutes for the error to appear.

When an error occurs, the inverter will stop (except with Modbus communication error) and set the relay. If the inverter 
is able to retry a start again (count < maxCount for that error) then it is considered a warning. In this case, the inverter 
will inform with the warning LED sequence and will clear the relay when retrying. It will also set the warning bit in 
WarningContents. The user must power reset or reset faults to clear the warnings (both LEDs and register). Modbus 
communication error will never stop the inverter and will only show as a warning.

When an error has occurred enough that count >= maxCount then the inverter will stop trying to start. In this case it 
will blink with the error LED sequence leave the relay set. At this point the inverter must be reset or the fault clear to 
start operation again.

A summary of errors is given below.

Summary of Contents for NOVA drive 370

Page 1: ...Systemair NOVA drive 370 Product Description...

Page 2: ...have a minimum shaft speed of 0 2rpm By external gear wheel it can run exchangers from 0 02 20rpm Control signal 0 10V Modbus RTU have an un linear function to ensure a linear heat transfer Extract su...

Page 3: ...Product description 4 3 Environmental constraints 4 4 Technical data 5 5 Mechanical and electrical installation 7 6 Motor parameters 11 7 LED behaviour 12 8 Fault behaviour 12 9 RHC features 13 10 Mo...

Page 4: ...the electrical installation on the rating plate matches the power supply Please refer to Table 2 for maximum fuse ratings and type CAUTION Risk of hot surfaces and electric shock if the unit has been...

Page 5: ...utral or phase to phase earth ground Frequency Hz 50 Hz 2 Hz Max input current 230V supply Arms 3 6 External input fuse size Type MAX C16 Minimum supply without speed reduction Vrms 207 Minimum supply...

Page 6: ...RS485 24V protected Control interface alarm 1x Alarm relay NC C NO Maximum 2A 250Vac or 6A 24Vdc Indicators Red Green Yellow LED on the PCB check Figure 6 for position Settings Dipswitch for Motor se...

Page 7: ...entation shall be vertical with the cable glands facing downwards This is to ensure the best thermal performance of the product For reference please refer to Figure 2 Figure 2 Mounting orientation of...

Page 8: ...Motor U V W Supply N L Alarm NC COM NO Solid wire 1 2 0 2 4 0 mm2 26 12 AWG Stranded wire 1 0 2 2 5 mm2 26 14 AWG Flat blade max 3 5 mm Analogue Control 0V Uin Uout Rotary Sensor 0V RUN DIR MODBUS 0V...

Page 9: ...ing Grounding hazard For the operator safety it is important to ground the drive properly and follow the provided grounding guidelines RCD compatibility For extra safety protection a Residual Current...

Page 10: ...anner until power is reset Enable rotary guard To use the rotary guard the sensor must be supplied with 10 V from Uout 10V and connected to ground 0V The out put from the sensor must be connected to R...

Page 11: ...if you wish to change the direction the motor rotates Note that the direction will change the next time the motor starts not when it is already rotating Maximum speed can be reduced and set as 50 100...

Page 12: ...how the latest error as it has higher priority Rotary guard Rotary guard passed When the rotary guard passes it shows the red green red green sequence 200ms each LED If the inverter has no warnings or...

Page 13: ...9 for a diagram When the inverter is running the motor and the rotary input is high for more than 10 seconds the functionality is disabled At this point a power reset is needed to enable it again 9 2...

Page 14: ...owing Modbus registers are available All the registers are either input registers 16 bit read only denoted by R or holding registers 16 bit read write denoted by RW Register Address Type Description B...

Page 15: ...rd in 0x115 R Rotor guard value 0 or 1 Test running 0x116 R 1 when test is running 0 otherwise Speed external 0 10V 0x117 R 0 4095 speed input Trimmer 0 10V 0x118 R 0 4095 trimmer input Extended SW ve...

Page 16: ...Safety req Automatic electrical controls for household and similar use EN 60335 2 40 2004 A11 2014 A12 2005 Safety req Particular requirements for electrical heat pumps air conditioners and dehumidifi...

Page 17: ...286rpm Current 0 79 0 46A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 2 8 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation...

Page 18: ...ent 1 37 0 79A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 5 5 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation direction...

Page 19: ...rent 2 04 1 18A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 8 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation direction C...

Page 20: ...no www systemair no Systemair B V Zanddonkweg 7a 5144 NX Waalwijk NETHERLANDS Tel 31 0 85 00 66 200 info systemair nl www systemair nl Systemair HVAC Spain S L U C Montecarlo 14 Fuenlabrada ES 28942...

Reviews: