PI controller 

Address 

Access  Description 

Resolution / Unit 

Default 

277 

0x0115 

Read-only 

Controller mode Comfort : 

0b0000 0000=controller off 

(Frost protection active)

 

0b0000 0001=controller auto mode 

(heating&cooling)

 

0b0000 0010=controller heating mode only 

0b0000 0011=controller cooling mode only 

0b0000 0100=ventilating 

(PI loop controls fan stages only, 

valves closed)

 

 

 

Controller mode ECO: 

0b0001 0000=controller off 

(Frost protection active)

 

0b0001 0001=controller auto mode 

(heating&cooling)

 

0b0001 0010=controller heating mode only 

0b0001 0011=controller cooling mode only 

0b0001 0100=ventilating 

(PI loop controls fan stages only, 

valves closed)

 

 

 

 

278 

0x0116 

Read-write 

Fan coil type

 

0b00000000= 2-pipe:cooling&heating with Change-Over  

0b00000001= 4-pipe:cooling&heating 

 

 

279 

0x0117 

Read-write 

Fan stages and operation modes

 

0b00000000 = none, 

(fan key is locked the fan symbol will 

be faded on the LCD)

 

0bxxxx0001 = single stage 

0bxxxx0010 = 2 stages 

0bxxxx0011 = 3 stages 

0b0001xxxx = fan works not in heating mode 

0b0010xxxx = fan works not in cooling/ventilation mode 

(0b0011xxxx = fan works not in heating & cooling mode)

 

 

 

280 

0x0118 

Read-write 

Start fan at highest stage for (_) seconds

 

0…60 = 0…60 seconds 

1.0 

281 

0x0119 

Read-write 

Fan OFF-Delay 

0= fan never stops 

1..255 = Fan stops 1…255 minutes after valves closing 

1.0 

min 

15 

282 

0x011A 

Read-write 

PWM Cycle time

 

0 = for 2-point control 

1…255 = PWM cycle time 1…255 minutes 

 

 

15 

283 

0x011B 

Read-write 

Deadband

 

1...100 = 0,1…10,0 °C/°F 

0.1 

°C/°F 

10 

284 

0x011C 

Read-write 

Heating Proportional Band Xp_heat

 

1...100 -> 0,1…10,0°C 

0.1 

°C/°F 

20 

285 

0x011D 

Read-write 

Heating Integration Time Tn_heat

 

0...255 = 0…255 Minutes 

1.0 

min 

30 

286 

0x011E 

Read-write 

Cooling Proportional Band Xp_cool

 

1…100 -> 0,1…10,0°C/°F 

0.1 

°C/°F 

20 

287 

0x011F 

Read-write 

Cooling Integration Time Tn_cool 

0…255 = 0…255 Minutes

 

1.0 

min 

30 

288 

0x0120 

Read-write 

Minimal limit of the control variable heat

 

0..100 

1.0 

289 

0x0121 

Read-write 

Maximal limit of the control variable heat

 

0..100 

1.0 

100 

290 

0x0122 

Read-write 

Minimal limit of the control variable cool

 

0..100 

1.0 

291 

0x0123 

Read-write 

Maximal limit of the control variable cool

 

0..100 

1.0 

100 

292 

0x0124 

Read-write 

Fan stage 1 ON threshold control variable heat

 

0..100 

1.0 

293 

0x0125 

Read-write 

Fan stage 2 ON threshold control variable heat

 

0..100 

1.0 

35 

294 

0x0126 

Read-write 

Fan stage 3 ON threshold control variable heat

 

0..100 

1.0 

70 

295 

0x0127 

Read-write 

Fan stage 1 ON threshold control variable cool

 

0..100 

1.0 

296 

0x0128 

Read-write 

Fan stage 2 ON threshold control variable cool

 

0..100 

1.0 

35 

297 

0x0129 

Read-write 

Fan stage 3 ON threshold control variable cool

 

0..100 

1.0 

70 

298 

0x012A 

Read-write 

Frost protection temperature threshold 

50..150 = +5,0..+15,0 °C 

400..600 = +40..+60 °F (257 – 0x0101 = 1)

 

0.1 

°C/°F 

70 / 

450

 

299 

0x012B 

Read-write 

Change-Over Temperature Threshold for Heating

 

0..500 = 0..+50,0 °C 

300..1200 = +30..+120,0 °F (257 – 0x0101 = 1)

 

0.1 

°C/°F 

300 / 

860

 

300 

0x012C 

Read-write 

Change-Over Temperature Threshold for Cooling 

0..500 = 0..+50,0 °C 

300..1200 = +30..+120,0 °F (257 – 0x0101 = 1)

 

In case temperature is in between both thresholds the last 

state will be maintained

 

0.1 

°C/°F 

190 / 

660

 

304 

0x0130 

Read-write 

Valve type selection

 

0= ON-OFF (ON = Valve Open, OFF = Valve Closed) 

1=PWM  (0%= 0%PWM  ..  100%  = 100% PWM) 

2= OFF-ON (OFF = Valve Open, ON = Valve Closed) 

 

 

 

Summary of Contents for LCF02 5DO RS485 Modbus

Page 1: ...odifications are prohibited The product must not be used in relation with any equipment that in case of a failure may threaten directly or indirectly human health or life or result in danger to human beings animals or assets Ensure all power is disconnected before installing Do not connect to live operating equipment CAUTION Risk of electric shock due to live components within the enclosure especi...

Page 2: ...erature in the room is lower for example The quicker the dynamics of the wall temperature acceptance of the wall or the longer the selected inquiry interval of the temperature sensor is the smaller the deviations limited in time are TECHNICAL DATA Measuring values temperature Output switch contact terminal 2 3 for heating cooling 2 point control or PWM 2 normally open contacts max 250 V 3 A max 30...

Page 3: ...nput terminals of the field devices are connected with each other and all negative operating voltage input terminals reference potential are connected together in phase connection of field devices In case of reversed polarity at one field device a supply voltage short circuit would be caused by that device The consequential short circuit current flowing through this field my cause damage to it The...

Page 4: ...r setting will be exited to normal operation No Name of parameter Parameter definition Factory default 1 Modbus address ID 1 ID 247 1 2 Baud rate 1 4800bps 2 9600 3 19200 4 38400 2 3 Parity 0 none 1 even 2 odd 0 4 Stop Bits 1 1 Stopbit 2 2 Stopbits 2 5 Temperature Offset Internal Sensor 5 0 K 5 0 K 0 6 Temperature Offset External Sensor 5 0 K 5 0 K 0 7 Piping system 0 2 pipe 1 4 pipe 1 8 Reset to ...

Page 5: ... time Then it will switch from ECO to comfort mode To indicate that the Fancoil thermostat is in ECO mode it will show the leaf and the word ECO in the display In case an occupancy sensor is connected to one of the inputs the mode will change from ECO to comfort as soon as the input becomes active and the previously used Setpoint will be restored and the leaf symbol will not be showing any more Te...

Page 6: ...M while the power failure so no data will be lost The setpoint is not saved The standard setpoint after power on reset applies register address 271 0x010F Occupancy OCC If the input is configured for an Occupancy sensor If the sensor indicates UnOccupied the current setpoint will be replaced by the Eco Mode Setpoint Temp The display will show the leaf symbol and the lettering ECO to indicate the E...

Page 7: ...ium 0b00000100 Stage High 0b00001000 Auto OFF 0b00001001 Auto Low 0b00001010 Auto Medium 0b00001100 Auto High 5 0x0005 Read only VA1 status 0 100 0 0 Off 100 On e g 693 69 3 of PWM cycle time ON 6 0x0006 Read only VA2 status 0 100 0 0 Off 100 On e g 693 69 3 of PWM cycle time ON 8 0x0008 Read only external temperature sensor C 200 1000 20 0 100 0 C 0 2100 0 0 210 0 F 257 0x0101 1 0 1 C F 9 0x0009 ...

Page 8: ... 200 F 257 0x0101 1 0 1 C F 0 C 320 F 268 0x010C Read write Power failure 0 keep off after power on reset 1 return to last state after power failure 2 switch on after power on reset 1 269 0x010D Read write Key lock 0x00 unlocked 0x01 lock on off 0x02 lock mode 0x04 lock clock 0x08 lock fan speed 0x10 lock temp setting 0x1F lock all keystrokes Once a locked key is pressed the LOCK symbol shall be d...

Page 9: ...d write Deadband 1 100 0 1 10 0 C F 0 1 C F 10 284 0x011C Read write Heating Proportional Band Xp_heat 1 100 0 1 10 0 C 0 1 C F 20 285 0x011D Read write Heating Integration Time Tn_heat 0 255 0 255 Minutes 1 0 min 30 286 0x011E Read write Cooling Proportional Band Xp_cool 1 100 0 1 10 0 C F 0 1 C F 20 287 0x011F Read write Cooling Integration Time Tn_cool 0 255 0 255 Minutes 1 0 min 30 288 0x0120 ...

Page 10: ...ssed disable cooling 10 Dew Point Sensor Closed Dewpoint crossed disable cooling 0 337 0x0151 Read write Configuration external input 2 0 No function 1 Occupancy sensor Open Occupied 2 Occupancy sensor Closed Occupied 3 Window contact Open Window Open 4 Window contact Closed Window Open 5 Disable heating Open Heating disabled 6 Disable heating Closed Heating Disabled 7 Disable cooling Open Disable...

Page 11: ...0x0101 1 0 1 C F 0 514 0x0202 Read write Controller mode Comfort 0b0000 0000 controller off Frost protection active 0b0000 0001 controller auto mode heating cooling 0b0000 0010 controller heating mode only 0b0000 0011 controller cooling mode only 0b0000 0100 ventilating PI loop controls fan stages only valves closed 0 Controller mode ECO 0b0001 0000 controller off Frost protection active 0b0001 00...

Page 12: ...de email thermokon de LCF02 5DO_Datasheet_en docx 2021 MOUNTING ADVICE DIMENSIONS MM For installing or maintenance please make sure the power is disconnected Fix the thermostat base plate to the wall through the four screw holes with distance between axes of 60 mm Fasten base plate and front cover Do not press the panel in order to protect LCD ...

Reviews: