Chapter 3 Deployment
Manual VIPA System SLIO
3-6
HB300E - IM - RE_053-1DN00 - Rev. 11/21
The System SLIO modules may also be parameterized by the configuration
tool.
For this your DeviceNet couple must be connected active at the bus.
For parameterization and for the access to the diagnostics data the data
type SHORT_STRING is used. Please consider that your DeviceNet
manager supports this type of data.
In your configuration tool you may parameterize your module by means of
a character string.
You also may transfer the current parameters from the module into your
configuration tool to adapt them and write them back to the module.
•
Each DeviceNet-Slot is separately be parameterized with a character
string.
•
Within the character string each parameter consists of a
Type
with
attached
Value
.
•
The parameters themselves are to be separated by a blank.
•
There are only parameter strings with lower case supported.
Depending on the type hexadecimal, decimal or binary values may be
preset
Type Meaning Value as
Range of values
Character
string
Example
Number
x
1Byte hexadecimal
00h ... FFh
x
hh
xA2
2x
2Byte hexadecimal
0000h ... FFFFh
2x
hhhh
2x7FFF
4x
4Byte hexadecimal
00000000h ... FFFFFFFFh 4x
hhhhhhhh
4x7FFF80C0
+
1Byte decimal positive 0 ... 255
+
ddd
+255
2+
2Byte decimal positive 0 ... 65535
2+
ddddd
2+65535
4+
4Byte decimal positive 0 ... 4294967295
4+
dddddddddd
4+4294967295
-
1Byte decimal negative -128 ... -1
-
ddd
-128
2-
2Byte decimal negative -32768 ... -1
2-
ddddd
2-32768
4-
4Byte decimal negative -2147483648 ... -1
4-
dddddddddd
4-2147483648
b
1Byte binary
00000000 ... 11111111
b
bbbbbbbb
b10100101
The analog module 031-1BB90 has 18byte parameter data. For the
parameterization with default values this results in the following string:
x00 x00 x00 x00 x00 x02 xC1 x02 2x7FFF 2x8000 xC1 x02 2x7FFF 2x8000
Note!
As soon as the parameter data do not fit to the sequence of the modules
on the System SLIO bus, the DeviceNet coupler goes to an error state and
signals this with its status LEDs.
Due to the system, modules which are not yet parameterized are supplied
with their default parameters as soon as you start a read access from your
configuration tool.
Accessing the
parameter data
Rules for the
parameterization
Example
Summary of Contents for SLIO IM 053-1DN00
Page 1: ...VIPA System SLIO IM 053 1DN00 Manual HB300E_IM RE_053 1DN00 Rev 11 21 May 2011...
Page 4: ...Contents Manual VIPA System SLIO ii HB300E IM RE_053 1DN00 Rev 11 21...
Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E IM RE_053 1DN00 Rev 11 21...
Page 28: ...Chapter 1 Basics and Assembly Manual VIPA System SLIO 1 20 HB300E IM RE_053 1DN00 Rev 11 21...