background image

REGISTER MAP

Data can be read using the Read Holding Registers command. A memory map de-

tailing all useful locations is listed below:

Notes: [1] See table in next section for possible values in this register. [2] A value 

0-255 will result in zero brightness (0) to maximum brightness (255). Any value lar-

ger than 255 is internally set to 255. [3] This register reflects the status of the input 

pins. The pins do not control anything, but can be used to read the status of exter-

nal equipment.

Pin numbers

The input status register reflects the value of the input pins. Toggling these pins 

while the unit is configured as a Modbus device does not affect the operating 

behavior.

Light effect types

The input status register reflects the value of the input pins. Toggling these pins 

while the unit is configured as a Modbus device does not affect the operating be-

havior.

ATEX Beacon 

D e t e c t i o n

 Bit 

Decimal value 

Pin

 Bit 3 

Red

 Bit 2 

Green

 Bit 1 

Blue

 Bit 0 

Yellow

 ID 

Effect

 0 

Slow flashing (3Hz 50% duty)

 1 

Looping effect 1

 2 

Looping effect 2

 3 

All leds continuously on

 4 

Looping effect 3

 5 

Flashing (2Hz 10% duty)

 6 

Flashing (10Hz 50% duty)

 Address 

Content 

Unit

 0x0000 

Light effect type 

View note [1]; 16 bit unsigned integer

 0x0001 

Red value 

View note [2]; 16 bit unsigned integer

 0x0002 

Green value 

View note [2]; 16 bit unsigned integer

 0x0003 

Blue value 

View note [2]; 16 bit unsigned integer

 0x0004 

Relay control 

zero: disabled, non-zero: energized

 0x0005 

Input status 

View note [3]; 16 bit unsigned integer

 0x0006 

Firmware version

M

A

N

U

A

L

Summary of Contents for ATEX BEACON

Page 1: ...D e t e c t i o n Manual Atex Beacon 78 Ultra bright RGB LEDs Colour selectable patterns Partnr ATEX BEACON M A N U A L...

Page 2: ...t the ATEX Beacon 3 PCB layout 4 Installation 5 Analogue controlled 5 Modbus controlled 6 Settings 6 Supported codes 6 Register map 7 Pin numbers 7 Light effect types 7 Specifications 8 Troubleshootin...

Page 3: ...disposal advice as regional variations apply You may return the unit to us for safe dismantling and disposal IMPORTANT This user manual contains important information regarding the operation of the A...

Page 4: ...ut Power supply 9 30V DC min 9W Stand by current 0 1W Trigger voltage positive 6 30V DC Trigger voltage ground min 6V DC below supply Trigger current max 6mA Cable diameter 0 25mm2 to 3 0 mm2 12 to 24...

Page 5: ...ct if you want to use the beacon analogue or controlled by Modbus ANALOGUE CONTROLLED Select the if the trigger is positive or negative trigger by setting the Jumper to the right position Select the m...

Page 6: ...scription DIP switch Modbus ID 0 disabled 1 255 Select Modbus 5 12 adres Baudrate 9600 9600 19200 Baudrate in 2 symbols per second Function Function name Used for code 3 Reading holding register s Rea...

Page 7: ...Light effect types The input status register reflects the value of the input pins Toggling these pins while the unit is configured as a Modbus device does not affect the operating be havior ATEX Beac...

Page 8: ...ct Colour selection EX mark II 2 GD Ex d IIC T6 INERIS 01ATEX0072x Can be used in zone 1 2 21 and 22 Meets the standard IEC60079 and EN60079 Troubleshooting Error Solution Beacon will not turn on Chec...

Page 9: ...0 94 1 0 0 1 1 1 1 0 158 1 1 0 1 1 1 1 0 222 0 0 0 1 1 1 1 1 31 0 1 0 1 1 1 1 1 95 1 0 0 1 1 1 1 1 159 1 1 0 1 1 1 1 1 223 0 0 1 0 0 0 0 0 32 0 1 1 0 0 0 0 0 96 1 0 1 0 0 0 0 0 160 1 1 1 0 0 0 0 0 22...

Reviews: