11
Object number
11
Name
DRY mode
Function
On/off
Description
This communication object reads the operation mode status of the AC unit connected to
system 1, switching to DRY mode when the value is ON and returning to the previous mode
when the mode value is OFF.
This mode can be only activated when it is available in the AC unit to which the system is
connected.
Values
Off
Dry mode Off; On
Dry mode On
Type of access to the Bus Reading/Writing
Data point identification
1,001
Object number
12
Name
DRY mode
Function
On/off
Description
This communication object activates/deactivates the operation mode of the AC unit
connected to system 1, switching to DRY mode when the value is ON and returning to the
previous mode when the mode value is OFF.
This mode can be only activated when it is available in the AC unit to which the system is
connected.
Values
Off
Dry mode Off; On
Dry mode On
Type of access to the Bus Writing
Data point identification
1,001
Object number
13
Name
VENTILATION speed of the system
Function
Speed of the system changeover
Description
This object is used to read the value of the ventilation speed set in the system in installations
Values
0%
Automatic; (1%-33%)
Speed 1; (34%-66%)
Speed 2; (67%-100%)
Speed 3
Type of bus access
Reading
Data point identification
5,001 (DPT_Scalling)
Object number
14
Name
VENTILATION speed of the system
Function
Speed of the system changeover
Description
This object is used to read or write the value of the ventilation speed set in the system in
installations
Values
0%
Automatic; (1%-33%)
Speed 1; (34%-66%)
Speed 2; (67%-100%)
Speed 3
Type of bus access
Writing
Data point identification
5,001 (DPT_Scalling)