BE1-BPR

3

Figure 1 - Functional blocks in BPR

PROGRAMMING LANGUAGE

The powerful nature of the BESTlogic programming language can be shown by the simple program used to
achieve the logic shown in Figure 2. The program is as follows:

LN=BFL2E

LI6=4,12

LOA=T4+O14+O15*

LO9=T3I6

LF1=PI,1

LI7=4,12

LO1=O2

LO10=I6+O11

LF2=NI,1

LR=0,0,0,0,0

LO2=T1O7+F1T2+O1O7

LO11=I3+I4+IT5

LF3=PI,2

LT=D,O8,/O8

LO3=O13

LO12=F3I1

LI1=4,12

LT2=D,O9,/O9

LO4=T5

LI2=4,12

LT3=C,O10,/O10

LO5=T3

LI3=4,12

LT4=D,O6,/O6

LO6=/I1/I2

LI4=4,12

LT5=D,O12,/O12

LO7=F1+F2

LI5=4,12

LT6=0,0,0

LO8=T3O11

*The non-maskable alarms are always ORed with the programmable diagnostics to aprovide an alarm output.

The BESTlogic commands provide an easy way to define functional elements and use them in logical expressions
to achieve the operation desired. Once programmed, different logic sets are activated simply by changing the
name of the active logic set using the LOGIC command. Please see the instruction manual for details.

FUNCTIONAL BLOCKS

Summary of Contents for BE1-BPR-309

Page 1: ...able inputs and outputs for virtually any application Four AC current and seven isolated contact inputs five control plus one alarm output RS 232 and RS 485 communication ports User may program the un...

Page 2: ...n cycle of 60 Hz Pickup setting on arc detector can be set below 0 1 A Isolated communications ports IRIG B time code input to set and synchronize on board real time clock Standard model relays have t...

Page 3: ...12 F3I1 LI1 4 12 LT2 D O9 O9 LO4 T5 LI2 4 12 LT3 C O10 O10 LO5 T3 LI3 4 12 LT4 D O6 O6 LO6 I1 I2 LI4 4 12 LT5 D O12 O12 LO7 F1 F2 LI5 4 12 LT6 0 0 0 LO8 T3O11 The non maskable alarms are always ORed w...

Page 4: ...dow of opportunity 2 Single Pole Tripping BF Logic Features Output latch in provided and Control timer limits operational window If single pole tripping is used a BFI input is available IN6 to start d...

Page 5: ...UT3 6 Retrip Output A Retrip output is provided to give a backup trip signal to the breaker trip coil This can either provide a separate path to a single trip coil or be hooked to the backup trip coil...

Page 6: ...BE1 BPR 6 Figure 7 Panel Cutout Dimensions Vertical Unit Figure 5 Panel Cutout Dimensions Horizontal Unit Figure 8 Rear View Vertical Unit Figure 6 Rear View Horizontal Unit DIMENSIONS...

Page 7: ...30 A for 0 2 sec carry 7 A continuously and break 7A 250Vdc Make and carry 30A for 0 2 sec carry 7A continuously and break 0 3A TARGETS Five diagnostic LEDs are provided plus target display of all I O...

Page 8: ...info basler com ORDERING INFORMATION PART NUMBER VERTICAL HORIZONTAL POWER SUPPLY CONFIGURATION BE1 BPR 309 BE1 BPR 300 48 125 Vac dc Basic model BE1 BPR 311 BE1 BPR 302 48 125 Vac dc Enhanced model...

Reviews: