Manual_GK473_DeviceNet_EN.doc
12/31
Baumer IVO GmbH & Co. KG
04.05.11
Villingen-Schwenningen,
Germany
Message Router Object, Class 0x02
Implemented but no visible attributes or services.
DeviceNet Object, Class 0x03
Class Attributes
Attribute ID
Access Rule
Name
DeviceNet
Data type
Value
1 Get Revision
UINT 0x0002
Class Services
Service Code
Get Attribute Single
0x0E
Instance Attributes
Attribute ID
Access Rule
Name
DeviceNet
Data type
Value
1 Get MAC
ID
UISNT
2
Get
Baud Rate
USINT
3 Get
BOI (Bus Off Interrupt)
BOOL
4
Get
Bus Off Counter
USINT
5 Get Allocation
Information
STRUCT
of:
Allocation choice Byte
Byte
Master’s MAC ID
USINT
6
Get
MAC ID Switch changed
BOOL
7
Get
Baud Rate Switch changed
BOOL
8
Get
MAC ID Switch Value
USINT
9
Get
Baud Rate Switch Value
USINT
Instance Services
Service Code
Get Attribute Single
0x0E
Set Attribute Single
0x10
Allocate Master/Slave connection
Set
0x4B
Release Master/Slave connection
Set
0x4C
Assembly Object, Class 0x04
Class Attributes
Attribute ID
Access Rule
Name
DeviceNet
Data type
Value
1 Get Revision
UINT 0x0002
Class Services
Service Code
Get Attribute Single
0x0E
Instance Attributes – Instance/Connection 0x65
Attribute ID
Access Rule
Name
DeviceNet
Data type
Value
3 Get
RS485 Subbus, SPA status information
complete
ARRAY[48] of
USINT
Instance Services
Service Code
Get Attribute Single
0x0E