59
EtherNet/IP On-Board Communications
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
AC/DC drive object, class 0x2a
This object models the functions specific to an AC or DC Drive, e.g., speed ramp, torque control, and so on.
Table 73. Motor data object
ID
Description
Data type
Access rule
Default
Class attributes
01h
Revision
UINT
Get
1
02h
Max instance
UINT
Get
1
03h
Number of instances
UINT
Get
1
Class services
0Eh
Get_attribute_single
Instance attributes
Default, Min./Max.
03h
AtReference
BOOL
Get
0
04h
NetRef
BOOL
Get/Set
0
06h
DriveMode
USINT
Get
0
07h
Speed Actual
INT
Get
0
08h
SpeedRef
INT
Get/Set
0
0Bh
Torque Actual
INT
Get
0
0Ch
TorqueRef
INT
Get/Set
0
1Dh
RefFromNet
BOOL
Get
0
12h
Accel time
UINT
Get
468,1,46875
13h
Decel time
UINT
Get
468,1,46875
0Ah
Currentlimit
INT-NV
Get/Set
345
64h
Accel time 1
UINT-NV
Get/Set
468,1,46875
65h
Accel time 2
UINT-NV
Get/Set
468,1,46875
66h
Decel time 1
UINT-NV
Get/Set
468,1,46875
67h
Decel time 2
UINT-NV
Get/Set
468,1,46875
1Ch
Time scale
SINT-NV
Get/Set
6,0,127
Instance services
Default
0Eh
Get_attribute_single
10h
Set_attribute_single
ote:
N
Final Accel Time = Accel Time 1 x (2 to power Time Scale).
Summary of Contents for PowerXL Series
Page 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Page 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Page 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...