Implemented CIP™ objects
General CIP objects
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Instance error messages
Supported service codes
Error
code
[hex]
Extended
code
[hex]
Error designation
Description
0x000
-
SUCCESS
No error
0x001
0x106
OWNERSHIP_CONFLICT
The connection could not be established because another
connection has already occupied the required resources. It is
only possible to establish an "exclusive owner" connection to
the adapter.
0x001
0x119
NON-
LISTEN ONLY CONNECTION
NOT OPENED
The connection could not be established because there is no
"non-listen only" connection (input only, exclusive owner).
The "non-listen only" connection must be of the "multicast"
connection type.
0x001
0x127
INVALID_ORIGINATOR_TO_
TARGET_SIZE
The resulting length of the ports mapped in the receive
object PDO_RX0 does not correspond to the number of data
bytes of the assembly object instance 110 (0x6E, Custom
Output) defined in the scanner.
0x001
0x128
INVALID_TARGET_TO_
ORIGINATOR_SIZE
The resulting length of the ports mapped in the transmit
object PDO_TX0 does not correspond to the number of data
bytes of the assembly object instance 111 (0x6F, Custom
Input) defined in the scanner.
0x001
0x204
UNCONNECTED_REQUEST_
TIMED_OUT
The adapter does not respond to the establishment of the
connection.
• There might be no physical connection.
• The adapter is switched off.
• The adapter has an invalid IP configuration.
0x001
0x320
ACCESS_CONTENTION
Manufacturer-specific error:
• The configurations of the assembly input and output
objects are mixed up.
• The connection could not be established because another
connection has already occupied the required resources.
It is only possible to establish an "exclusive owner"
connection to the adapter.
0x001
0x111
ROUTER_EXT_ERR_RPI_
NOT_SUPPORTED
The RPI set for a connection is not supported.
• Min. class 1 RPI = 4 ms
• Min. class-3-RPI = 10 ms
0x001
0x112
RROUTER_EXT_ERR_RPI_
VALUE_NOT_ACCEPTABLE
The RPI set for a connection is not supported.
• Min. class 1 RPI = 4 ms
• Min. class-3-RPI = 10 ms
0x001
0x123
ROUTER_EXT_ERR_INVALID_
TO_CONNECTION_TYPE
The output image connection type is invalid or not
supported.
0x001
0x124
ROUTER_EXT_ERR_INVALID_
TO_CONNECTION_TYPE
The input image connection type is invalid or not supported.
0x001
0x12A
ROUTER_EXT_ERR_INVALID_
CONSUMING_PATH
The path specification for the output data from the scanner
is invalid.
0x001
0x12B
ROUTER_EXT_ERR_INVALID_
PRODUCING_PATH
The path specification for the input data to the scanner is
invalid.
Service code
[hex]
Name
Description
0x54
Forward_Open
Opens a CIP connection from the PLC to the target drive.
0x4E
Forward_Close
Closes a CIP connection from the PLC to the target drive.
0x0E
Get_Attribute_Single
Outputs the value of a certain attribute.