COMMUNICATIONS INTERFACE
www.maxcessintl.com
DLCA NET-ECAT
MI 850A365 1
Page 49 of 72
8.6.1
Command request
Commands start at 0x0 and continue to 0x1FF.
Parameters start at 0x200 and continue to 0x3FF.
For parameters, add 0x1000 for a Write and 0x0000 for a Read to
the parameter number.
Command/parameter list
WO = Write Only, RO = Read only, RW = Read and Write
The parameter Class specifies which group this parameter
belongs to in the DLCA NET-ECAT. The class can be
communication (Comm), parameter (Parm), load cell calibration
(LC Cal), or output calibration (Out Cal). This classification is used
when resetting parameters to defaults with the NV Reset
commands.
Data types
int16 = signed 16-bit integer
uint32 = unsigned 32-bit integer
int32 = signed 32-bit integer
float = 32-bit single precision floating point number
Some commands and parameters are not useful for the two
tension zone DLCA NET-ECAT.
Command/
Parameter Number
Function or Parameter
Type
Class
Data Type
and R/W
Explanation
Hex
Decimal
0x000
0
Idle
Function
None
WO
0x001
1
Zero Calibrate Zone 1
Function
None
WO
0x002
2
Precision Calibrate Zone 1
Function
None
WO
See 9.1
0x003
3
Weightless Calibrate Zone 1
Function
None
WO
See 9.2
0x004
4
Zero Calibrate Zone 2
Function
None
WO
0x005
5
Precision Calibrate Zone 2
Function
None
WO
See 9.1
0x006
6
Weightless Calibrate Zone 2
Function
None
WO
See 9.2
0x007
7
Cal Output 0, 10V, 0%
Function
None
WO – int16
See 8.7.4
0x008
8
Cal Output 0, 10V, 100%
Function
None
WO – int16
See 8.7.4
0x009
9
Cal Output 0, 20mA, 0%
Function
None
WO – int16
See 8.7.4
0x00A
10
Cal Output 0, 20mA, 100%
Function
None
WO – int16
See 8.7.4
0x00B
11
Cal Output 1, 10V, 0%
Function
None
WO – int16
See 8.7.4
0x00C
12
Cal Output 1, 10V, 100%
Function
None
WO – int16
See 8.7.4
0x00D
13
Cal Output 1, 20mA, 0%
Function
None
WO – int16
See 8.7.4
0x00E
14
Cal Output 1, 20mA, 100%
Function
None
WO – int16
See 8.7.4
Command
Read or write