6. MODBUS REGISTERS
6 - 33
6.3.6 SDO Abort Code (2A60h)
(1) List of registers
Address Name
Data
type
Read/
write
No. of Points/
No. of Registers
Continuous read/
continuous write
2A60h
SDO Abort Code (SDO Abort Code)
4 bytes
Read
2
Impossible
The latest SDO Abort Code generated in Modbus communication can be read.
The access to registers can be checked by reading the latest SDO Abort Code.
When an error is found by reading SDO Abort Codes, change the method to access registers.
(2) Usage
Read SDO Abort Codes using this register.
The following table lists the SDO Abort Codes.
SDO Abort Code
Description
0000 0000h
No problem found.
0504 0001h
Client/server command specifier not valid or unknown.
0601 0000h
Unsupported access to a register.
0601 0001h
Attempt to read a write only register.
0601 0002h
Attempt to write a read only register.
0602 0000h
Register does not exist in the Modbus resisters.
0604 0041h
Resister cannot be mapped to the PDO
0604 0042h
The number and length of the resisters to be mapped would exceed PDO length
0607 0010h
Data type does not match, length of service parameter does not match
0609 0011h
Element of resister does not exist.
0609 0030h
Value range of parameter exceeded (only for write access).
0609 0031h
Value of parameter written too high.
0609 0032h
Value of parameter written too low.
0800 0000h
Generic error.
0800 0020h
Data cannot be transferred or stored to the application
0800 0021h
Data cannot be transferred or stored to the application because of local control.
0800 0022h
Data cannot be transferred or stored to the application because of the present device state.
0800 0024h
No data available.