NOVUS AUTOMATION
28/53
125
MQTT_LAST_UPDATE_MINUTE
Minute of last submission to the MQTT Broker.
126
MQTT_LAST_UPDATE_SECOND
Second of last submission to the MQTT
Broker.
136
WIFI_IRSS
Signal quality between the device and the Wi-
Fi Gateway.
Unit with signal in dB with two
decimal places.
137
WIFI_GATEWAY_COM_STATUS
Wi-Fi communication status.
0.
Disconnected Gateway;
1.
Connected Gateway;
2.
Gateway password error;
3.
Gateway not found;
4.
Error receiving IP via DHCP;
5.
Authentication error.
138
WIFI_MQTT_STATUS
Communication status with MQTT Broker.
0.
Disconnected Broker;
1.
Connected Broker;
2.
Error resolving DNS;
3.
Error when posting a
message in Broker;
4.
Error when subscribing to
topic.
140
WIFI_IP_ADDR_0_1
Address of the device on the network (High
part).
XXX.XXX.000.000
141
WIFI_IP_ADDR_2_3
Address of the device on the network (Low
part).
000.000.XXX.XXX
142
WIFI_MASK_ADDR_0_1
Network mask (High part).
XXX.XXX.000.000
143
WIFI_MASK_ADDR_2_3
Network mask (Low part).
000.000.XXX.XXX
144
WIFI_GATEWAY_ADDR_0_1
Network Gateway address (High part).
XXX.XXX.000.000
145
WIFI_GATEWAY_ADDR_2_3
Network Gateway address (Low part).
000.000.XXX.XXX
Table 09
– Registers Table
Below is the table of registers supported by the WRITE HOLDING REGISTERS and WRITE MULTIPLE HOLDING REGISTERS commands:
ADDRESS
MNEMONIC
DESCRIPTION
INFORMATION
68
BUZZER_STATUS
Current buzzer status.
0.
Inactive buzzer;
1.
Active buzzer.
1044
SETTING_YEAR
Year setting in UTC (GMT 0).
1045
SETTING_MONTH
Month setting in UTC (GMT 0).
1046
SETTING_DAY
Day setting in UTC (GMT 0).
1047
SETTING_HOUR
Hour setting in UTC (GMT 0).
1048
SETTING_MINUTE
Minute setting in UTC (GMT 0).
1049
SETTING_SECOND
Second setting in UTC (GMT 0).
1100
CHD_ALARM_MIN
Setting the digital channel minimum alarm.
Unit in counts.
1101
CHD_ALARM_MAX
Setting the digital channel maximum alarm.
Unit in counts.
1123
CH1_ALARM_MIN
Analog channel 1 minimum alarm setting.
Decimal places:
1.
For temperature sensors and
the cold joint;
2.
For battery voltage and
external power supply.
For linear sensors, the decimal
point is configured.
1124
CH1_ALARM_MAX
Analog channel 1 maximum alarm setting.
Decimal places:
1.
For temperature sensors and
the cold joint;
2.
For battery voltage and
external power supply.
For linear sensors, the decimal
point is configured.
1176
CH2_ALARM_MIN
Analog channel 2 minimum alarm setting.
Decimal places:
1.
For temperature sensors and
the cold joint;
2.
For battery voltage and
external power supply.
For linear sensors, the decimal
point is configured.