The variables above are:
NAME: the name of the sensor. You can put up to 20 characters.
UNIT: Units to meter the gas. There are two kinds of units in ppm or %LIE or %.
INCREASING: if the value is increasing or decreasing.
ZERO: Minimum (start up of scale). Default is 0.
RANGE: Maximum (maximum value of scale). The value range is from 20 to 300.
ALARM 1: Alarm 1 level.
ALARM 2: Alarm 2 level.
ALARM 3: Alarm 3level.
RELAY ALARM 1: the relay that will be activated when there is an Alarm 1 level at the sensor.
RELAY ALARM 2: the relay that will be activated when there is an Alarm 2 level at the sensor.
RELAY ALARM 3: the relay that will be activated when there is an Alarm 3 level at the sensor.
RELAY FAULT: the relay that will be activated when there is a fault at the sensor.
ZONE: the zone of the sensor.
At next table we can see some typical values.
Type
Gas
Zer
o
Limit Unit
Alarm 1
Alarm 2
Alarm 3
BS-380
LPG
0
20
%LIE 7
10
20
BS-381
Methane
gas
0
20
%LIE 6
10
20
BS-382
Carbon
Monoxide
0
300
ppm
25:50
100
200
BS-383
Ammonia
0
300
ppm
10
20
50:100
BS-390
LPG
0
20
%LIE 7
10
20
BS-391
Methane
gas
0
20
%LIE 6
10
20
BS-393
Ammonia
0
300
ppm
10
20
50:100
-
Oxygen*
0
25
%
18
19
22
TC-100N/LPG LPG
0
100
%LIE 8
12
20
TC-100N/CNG Methane
gas
0
100
%lie
8
12
20
*The parameter increase must be set to NO.
Relay programming
All the relays of panel are programmable for connecting any application.
The relay programming options in the
configuration of relay menu are shown below,
with Setup you can setup the relay from scratch, with Copy you can copy the setup from one relay to
another, and with Initialise you can load the default values.
==== RELAY =======
COPY RELAY
SELECT ENTER
====================
====== RELAY ======
INITIALISE RELAY
SELECT ENTER
====================
===== RELAY ======
SETUP RELAY
SELECT ENTER
====================