80
6
. Detailed settings for communications
6.3 CompoWay/F (continued)
■
Response frame
• The exit code is returned as the reply when 1 command frame is received when sent to this unit.
• There is no response if the command is not complete between ETX and BCC.
• The error detection priority is the order when more than one error occurs.
■
Example exit codes
The following is an example of exit codes when the command did not end normally.
For example: When there is no command text
Command
Response
The exit code will be "14" (format error).
Communication
address
Sub-address
Exit code
Command text
BCC
STX
0
0
ETX
Fixed Fixed
1
2
2
2
1
1
Exit
code
Name
Description
Error detection
Priority
00
Normal end
This indicates that the command ended normally and
that there was no error.
None
0F
FINS command error
The specified FINS command could not be executed.
Determine the reason for non-execution from the FINS
response code.
3
14
Format error
•
The numbers 0 to 9 and letters A to F are used in
command text (except in echo back tests).
•
There is no SID or command text. Alternatively, there is
no command text. MRC/SRC in the command text is
incomplete.
2
16
Sub-address error
•
The sub-address is invalid.
1
Communication
address
Sub-address
SID
BCC
STX
0
0
0
ETX
Communication
address
Sub-address
Exit code
BCC
STX
0
0
1
4
ETX