3.2.118 ERROR_LINE
/i
3.2.119 ERRORMASK
/i
3.2.120 ETHERNET
/i
Type
Task parameter (read-only)
Syntax
ERROR_LINE
Description
The
ERROR_LINE
parameter contains the number of the line which caused
the last BASIC run-time error in the program task. This value is only valid
when the
BASICERROR
parameter is
TRUE
.
Each task has its own
ERROR_LINE
parameter. Use the
PROC
modifier to
access the parameter for a certain task. Without
PROC
, the current task will
be assumed.
Arguments
N/A
Example
>> PRINT ERROR_LINE PROC(4)
23.0000
See also
BASICERROR
,
PROC
,
RUN_ERROR
.
Type
Axis parameter
Syntax
ERRORMASK
Description
The
ERRORMASK
axis parameter contains a mask value that is
AND
ed bit
by bit with the
AXISSTATUS
axis parameter on every servo cycle to deter-
mine if a motion error has occurred. If the result of the AND operation is not
zero, the motion error has occurred.
When a motion error occurs the enable switch (
WDOG
) will be turned off, the
MOTION_ERROR
parameter will have value different than 0 and the
ERROR_AXIS
parameter will contain the number of the first axis to have the
error.
Check the
AXISSTATUS
parameter for the status bit allocations. The default
setting of
ERRORMASK
is 268.
Arguments
N/A
Example
No example.
See also
AXIS
,
AXISSTATUS
,
MOTION_ERROR
,
WDOG
.
Caution
It is up to the user to define in which cases a motion error is gener-
ated. For safe operation it is strongly recommended to generate a
motion error when the Following Error has exceeded its limit in all
cases. This is done by setting bit 8 of
ERRORMASK
Type
System command
Syntax
ETHERNET(function, unit_number, parameter [,values])
Description
The command
ETHERNET
is used to read and set certain functions of Ether-
net communications. The
ETHERNET
command should be entered on the
command line of the terminal window of Trajexia Studio in disconnected
mode.
Note: The commands with parameters 4,5,7,9,10 and 12 take effect immedi-
ately after execution. The commands with parameters 0,2,3 and 8 require a
power cycle to Trajexia to enable the new parameters.