Data Library
2.2 Status Bits
ATC5300
18
Modbus Communication Protocol, Edition 03/2011, A5E02469001-02
¿
Reading the words starting at the address 40h will return 32 bits with the following meaning:
2.2
Status Bits
(To be used with functions 03 and 04)
38h
2
Number of operations of line 2 breaker
in AUT
nr
Unsigned long
3Ah
2
Number of switching alarms of
breaker 1
nr
Unsigned long
3Ch
2
Number of switching alarms of
breaker 2
nr
Unsigned long
3Eh
2
(not used)
—
Unsigned long
40h
2
Error bits
¿
bits
Unsigned long
Bit
Code
Alarm
0
A01
Battery voltage too low
1
A02
Battery voltage too high
2
A03
Line 1 circuit breaker timeout
3
A04
Line 2 circuit breaker timeout
4
A05
Line 1 wrong phase sequence
5
A06
Line 2 wrong phase sequence
6
A07
Load not powered timeout
7
A08
Generator not available
8
A09
Emergency
9
—
(not used)
10
—
Breaker 1 Trip
11
—
Breaker 1 Withdrawn
12
—
Breaker 2 Trip
13
—
Breaker 2 Withdrawn
14
…
31
—
(not used)
ADDRESS WORDS
FUNCTION
FORMAT
2070h
1
Front panel keyboard status
¿
Unsigned integer
2071h
1
Digital inputs status (by pin)
À
Unsigned integer
2072h
1
Digital outputs status (by pin)
Á
Unsigned integer
—
1
—
—
2074h
1
Line 1 voltage status
Â
Unsigned integer
2075h
1
Line 1 breaker status
Ã
Unsigned integer
2076h
1
Line 2 voltage status
Â
Unsigned integer
2077h
1
Line 2 breaker status
Ã
Unsigned integer
2078h
1
Input function status
Ä
Unsigned integer
207Ah
1
Output function status
Å
Unsigned integer