Data Library
2.3 Commands
ATC5300
Modbus Communication Protocol, Edition 03/2011, A5E02469001-02
21
Å
Following table shows meaning of bits of the word at address 207Ah:
2.3
Commands
(To be used with function 06)
¿
The following table shows the values to be written to address 2F00h to achieve the
correspondent functions.
À
Writing value 01 to the indicated address, the correspondent function will be executed.
Á
Writing value AAh to the indicated address, the correspondent function will be executed.
Â
Writing value FFh to the indicated address, the correspondent function will be executed.
Ã
The following table shows the values to be written to address 2F08h to achieve the
correspondent functions.
Bit
Output Functions Status
0
Line 1 breaker open
1
Line 1 breaker close
2
Line 2 breaker open
3
Line 2 breaker close
4
Global alarm
5
Generator 1 start
6
Generator 2 start
7
ATS ready
8
Load shed
9
Pre-transfer
10
Post-transfer
11
…
15
Not used
ADDRESS WORDS
FUNCTION
FORMAT
2F00h
1
Operative mode change
¿
Unsigned integer
2F01h
1
Device reset (warm boot)
À
Unsigned integer
2F02h
1
Setup parameters back to factory default
À
Unsigned integer
2F03h
1
Save parameters in EEPROM
Á
Unsigned integer
2F04h
1
Hour counter reset
Â
Unsigned integer
2F05h
1
Operation counters reset
Â
Unsigned integer
2F06h
1
Event log reset
À
Unsigned integer
2F07h
1
Save Real time clock setting
À
Unsigned integer
2F08h
1
Keyboard lock ON / OFF
Ã
Unsigned integer
—
—
—
—
2F0Dh
1
Front panel keystroke simulation
Ä
Unsigned integer
Value
Function
0
Switch to OFF mode
1
Switch to MAN mode
2
Switch to AUT mode
3
Switch to TEST mode