Description of blocks
3.2 Driver module DRV_3WL
Library SENTRON 3WL / 3VL for SIMATIC PCS 7
38
Function Manual, 11/2008, A5E02316914A-01
I/O (parameter)
Comment
Data type
Default
Type OCM
POS_CB
Position of circuit breaker
BYTE
0
O
x
QDISCON
1 = Disconnected
BOOL
FALSE
O
x
QOP_POS
1 = Operating position
BOOL
FALSE
O
QTEST_POS
1 = Test position
BOOL
FALSE
O
QNO_CB
1 = Circuit breaker not present
BOOL
FALSE
O
x
ST_CB
Status of circuit breaker
BYTE
0
O
x
QNOT_RDY
1 = Circuit breaker not ready
BOOL
FALSE
O
QOFF
1 = Main contacts disconnected
BOOL
FALSE
O
QON
1 = Main contacts closed
BOOL
FALSE
O
QTRIP
1 = Circuit breaker has tripped
BOOL
FALSE
O
QLOC_OFF
1 = Local turn off of circuit breaker
BOOL
FALSE
O
x
QRDY_ON
1 = Ready to switch on
BOOL
FALSE
O
QUNV_REL
1 = Voltage applied to undervoltage
release
BOOL
FALSE
O
QSPR_CHAR
1 = Storage spring is charged
BOOL
FALSE
O
QOVLD_WRN
1 = Overload warning present
BOOL
FALSE
O
QSP_EXCEED
1 = An activated setpoint value has been
exceeded
BOOL
FALSE
O
QWRN
1 = A warning signal is currently present
BOOL
FALSE
O
QWR_PROT
1 = Write operations are prohibited
BOOL
FALSE
O
QFREE_COM15
1 = Status of the free user input on the
COM15 module
BOOL
FALSE
O
LST_TRIP
Reason for last trip
BYTE
0
O
QTR_OVLD
1 = Overload tripping (L)
BOOL
FALSE
O
QTR_ISC
1 = Instantaneous short-circuit (I)
BOOL
FALSE
O
QTR_STD_C
1 = Short-time-delay short-circuit (S)
BOOL
FALSE
O
QTR_GF
1 = Ground fault (G)
BOOL
FALSE
O
QTR_EXT_F
1 = Trip as a result of extended protection
function
BOOL
FALSE
O
QTR_OVLD_N
1 = Overload in neutral conductor
BOOL
FALSE
O
QLD_SHED
1 = Load shedding warning
BOOL
FALSE
O
E_TIME_SYC
1 = Error time synchronization
BOOL
FALSE
O
STON_GFNA
Short time on / Ground fault off
BOOL
FALSE
O
x
STON_GFOFF_QC
Quality code of STON_GFOFF
BYTE
0
O
STON_GFOFF_NA
Short time on / Ground fault off not
available
BOOL
FALSE
O
x
STON_GFOFF_STOFF_GFON Short time off / Ground fault off
BOOL
FALSE
O
x
STOFF_GFON_QC
Quality code of STOFF_GFON
BYTE
0
O
STOFF_GFON_NA
Short time off / Ground fault on not
available
BOOL
FALSE
O
x
N_ACT_LD
DR 91: Number of switch actions under
load
WORD
0
O
x
N_ACT_LD_QC
Quality code of N_ACT_LD
BYTE
0
O