Description of blocks
3.3 Driver module DRV_3VL
Library SENTRON 3WL / 3VL for SIMATIC PCS 7
106
Function Manual, 11/2008, A5E02316914A-01
I/O (parameter)
Comment
Data type
Default
Type OCM
QLOC_OFF
1 = Local turn off of circuit breaker
BOOL
FALSE
O
x
QOVLD_WRN
1 = Overload warning present
BOOL
FALSE
O
QSP_EXCEED
1 = An activated setpoint value has been
exceeded
BOOL
FALSE
O
QWRN
1 = A warning signal is currently present
BOOL
FALSE
O
QWR_PROT
1 = Write operations are prohibited
BOOL
FALSE
O
LST_TRIP
Reason for last trip
BYTE
0
O
QTR_OVLD
1 = Overload tripping (L)
BOOL
FALSE
O
QTR_ISC
1 = Instantaneous short-circuit (I)
BOOL
FALSE
O
QTR_STD_C
1 = Short-time-delay short-circuit (S)
BOOL
FALSE
O
QTR_GF
1 = Ground fault (G)
BOOL
FALSE
O
QTR_OVLD_N
1 = Overload in neutral conductor
BOOL
FALSE
O
E_TIME_SYC
1 = Error time synchronization
BOOL
FALSE
O
STON_GFOFF
Short time on / Ground fault off
BOOL
FALSE
O
x
STON_GFOFF_QC
Quality code of STON_GFOFF
BYTE
16#80
O
STON_GFOFF_NA
Short time on / Ground fault off not available BOOL
TRUE
O
x
STOFF_GFON
Short time off / Ground fault on
BOOL
FALSE
O
x
STOFF_GFON_QC
Quality code of STOFF_GFON
BYTE
16#80
O
STOFF_GFON_NA
Short time off / Ground fault on not available BOOL
TRUE
O
x
N_ACT_LD
DR 91: Number of switch actions under load WORD
0
O
x
N_ACT_LD_QC
Quality code of N_ACT_LD
BYTE
16#80
O
N_ACT_LD_NA
DR 91: Number of switch actions under load
not available
BOOL
TRUE
O
x
N_ACT_TRP
DR 91: Number of switch actions caused by
a trip
WORD
0
O
x
N_ACT_TRP_QC
Quality code of N_ACT_TRP
BYTE
16#80
O
N_ACT_TRP_NA
DR 91: Number of switch actions caused by
a trip not available
BOOL
TRUE
O
x
N_SC_TRP
DR 91: Number of short circuit trips (SI)
WORD
0
O
x
N_SC_TRP_QC
Quality code of N_SC_TRP
BYTE
16#80
O
N_SC_TRP_NA
DR 91: Number of short circuit trips (SI) not
available
BOOL
TRUE
O
x
N_OVL_TRP
DR 91: Number of overload trips (L)
WORD
0
O
x
N_OVL_TRP_QC
Quality code of N_OVL_TRP
BYTE
16#80
O
N_OVL_TRP_NA
DR 91: Number of overload trips (L) not
available
BOOL
TRUE
O
x
N_EF_TRP
DR 91: Number of earth fault trips (G)
WORD
0
O
x
N_EF_TRP_QC
Quality code of N_EF_TRP
BYTE
16#80
O
N_EF_TRP_NA
DR 91: Number of earth fault trips (G) not
available
BOOL
TRUE
O
x
DIAG_WRN
DR 92: Active warnings
WORD
0
O
DIAG_WRN_QC
Quality code of DIAG_WRN
BYTE
16#80
O
WRN_NO1
Warning number 1
INT
0
O
x
WRN_NO2
Warning number 2
INT
0
O
x
Summary of Contents for SENTRON 3WL
Page 1: ...SENTRON 3WL 3VL Library for SIMATIC PCS 7 V1 0 Function Manual 11 2008 SIMATIC ...
Page 2: ......
Page 145: ......