Register
Parameter
Parameter
Scale
Scale
Notes
Address
Notation
Low
High
0
Reserved
1
HSP1
High Limit Set Point 1
*1
*1
R/W
2
LSP1
Low Limit Set Point 1
*1
*1
R/W
3
SP2
Set Point 2 value for output 2
*1
*1
R/W
4
Reserved
5
Reserved
6
PV.HI
Historical max. value of PV
*1
*1
R
7
PV.LO
Historical min. value of PV
*1
*1
R
8
Reserved
9
INPT
Input type selection
0
65535
R/W
10
UNIT
Process unit
0
65535
R/W
11
RESO
Display resolution
0
65535
R/W
12
IN.LO
Low scale value for linear input
*1
*1
R/W
13
IN.HI
How scale value for linear input
*1
*1
R/W
14
SNIF
PV shift (offset) value
*1
*1
R/W
15
FILT
PV filter time constant
0
65535
R/W
16
T.ABN
Accumulated time during abnormal condition
0
6553.5
R
17
OUT1
Output 1 function
0
65535
R/W
18
Reserved
19
Reserved
20
O1.HY
Output 1 hysteresis value
*2
*2
R/W
21
Reserved
R/W
22
Reserved
23
Reserved
24
Reserved
25
Reserved
26
Reserved
27
Reserved
28
HSP.L
Lower limit of HSP1
*1
*1
R/W
29
HSP.H
Upper limit of HSP1
*1
*1
R/W
30
LSP.L
Lower limit of LSP1
*1
*1
R/W
31
LSP.H
Upper limit of LSP1
*1
*1
R/W
32
Reserved
30
7-2 Exception Responses
If the controller receives a message which contains a corrupted character (parity check error, framing error etc.), or if
the CRC16 check fails, the controller ignores the message. However, if the controller receives a syntactically correct
message which contains an illegal value, it will send an exception response, consisting of five bytes as follows:
slave aoffset function code + exception code + CRC16 Hi +CRC16 Lo
Where the offset function code is obtained by adding the function code with 128 (ie. function 3 becomes H'83), and
the exception code is equal to the value contained in the following table:
Exemption Code
Name
Cause
1
Bad Function Code
Function code is not supported by the controller
2
Illegal data address
Register address out of range
3
Illegal data value
Data value out of range or attempt to write
a read-only or protected data
7-3 Parameter Table