background image

Texmate, Inc. Tel. (760) 598-9899  •  www.texmate.com

DL-40JANUS-SG manual (d0116)

Page 7

The Modbus/RS-485 communication settings sub-menu allows 

you to set the following parameters:
a) Baud Rate – this is the baud rate of the RS-485 serial communi-

cation between the meter (slave) and Modbus master. Options are 

9600 (default, meter shows “96”) and 19200 (meter shows “192”).
b) Address – this is the meter’s Modbus address on the RS-485 

loop. Typically, RS-485 limits the number of devices on the loop to 

32, but the DL-40 supports the full Modbus address range of 1-247. 

Address 1 is the default value.

c) Parity – this is the parity setting for the RS-485 serial commu-

nication between the meter (slave) and Modbus master. Options 

are: None (display shows “0”; Odd (display shows “1”); Even 

(default, display shows “2”).
The meter’s response time to a read command from the master is 

40-45msec (typically 42msec). The response time for a write com-

mand is 70-75msec (typically 72msec). This is due to the module 

having to communicate to the meter’s core firmware to complete 

the desired command. Exception responses are handled directly 

by the module and typically have a response time of 3msec.

Modbus RTU & RS-485 Communication Settings

The DL-40 Modbus communication module supports the following 

Modbus commands:

a) Read Holding Register (0x03)
b) Write Single Register (0x06)

Modbus addresses for DL-40JANUS registers are shown on 

the next page

The following are some things to note about particular registers:
a) Modicon address 40001 RELAY has the bit values for Sp3 & 

Sp4 and LED3 & LED4 reversed. There is an historical reason 

for this, and we have chosen to maintain backward compatibili-

ty in case customer’s want to send their meters in for a Modbus 

upgrade (at a nominal fee).

b) Modicon addresses 40002 INP, 40026 PEAK, 40027 VALY, 

40029 ZERO, 40029 SPAN return a 2 byte hexadecimal value 

of the meter’s display (in counts) and does not include the deci-

mal point. If you need the decimal value with decimal point, you 

will need to read the register, convert it to decimal, read 40024 

(see below) to determine decimal location, then combine the 

two. Display counts are in Two’s Complement notation.

   

a. Hex values for 0 to 9999 are 0x0000 to 0x270F.

   

b. Hex values for -1 to -1999 are 0xFFFF to 0xF831.

   

c. Over-range is indicated by a returned value of 9999  

 

   (0x270F).

   

d. Under-range is indicated by a returned value of -1999  

 

   (0xF831).

c) In order for Sp3 and Sp4 set point settings to work, the DL-40 

must have the optional Output Carrier Board installed (P/N 

SA-DL/OM-CB).

d) All Delay on Make (DoM), Delay on Break (DoB) and Hysteresis 

values are in units of whole seconds.

e) Modicon address 40023 RLYMOD uses the following values 

to set the relay activation mode (letter sequence is SP1, SP2, 

SP3, SP4):

   

a. 0 for HHHH

   

b. 1 for HLHL

   

c. 2 for LHLH

   

d. 3 for LLLL

   

e. H means relay is energized if input is equal to or  

             exceeds setpoint; L means relay is energized if input 

                  is less than setpoint.
   

f.  Note that the meter will not show the last two letters if 

                  the Output Carrier Board option is not installed.
f)  Modicon address 40023 DP uses the following values to set the 

display decimal point location:

   

a. 0 for XXXX (none)

   

b. 1 for XXXX.

   

c. 2 for XXX.X

   

d. 3 for XX.XX

   

e. 4 for X.XXX

g) Modicon address 40025 BRIGHT must be a value between 1 

(most dim) to 4 (most bright).

h) Modicon addresses 40028 and 40029 will have different mean-

ings depending on the Auto calibration or Manual rescaling 

operational selection (see Auto Calibration Mode or Manual 

Rescaling Mode above).  These are explained in the register 

table below.

i) Modicon addresses 40030 IZERO and 40031 ISPAN return 

hexadecimal values related to the Auto Mode calibration of the 

meter. They do not necessarily match expected values due vari-

ations and tolerances in the measurement circuit components, 

e.g., calibrating with a value of zero volts for the ZERO value 

may return a value of 0xFFFE (-2).  These registers have no 

meaning in Manual Rescaling Mode).

Modbus RTU Implementation

Summary of Contents for DL-40JANUS-SG

Page 1: ...utput Range Setting and Calibration 6 General Features Specifications Software Features Index LEOPARD FAMILY DL 40JANUS SG Two scaling methods MANUAL no external sig nal source required and AUTO requi...

Page 2: ...by pressing and releasing the or buttons When there are more than two display selec tions they are shown in brackets below the first display and are also selectable by press ing and releasing the or b...

Page 3: ...L POINT AND BRIGHTNESS SELECTION See Page 6 Setpoint 3 SP3 Setpoint 4 SP4 Valley Offset Scale Factor Calibrate Analog Output Lo Calibrate Analog Output Hi X XXX XX XX XXX X XXXX XXXX 2 3 4 Decimal Poi...

Page 4: ...t STEP B Select Between Calibration of Input or Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to se...

Page 5: ...Point Analog Output Note If the analog output option is not present Step B is skipped and the program goes directly from Step A to Step C 1 Press the or button to select the display toggling from CAL...

Page 6: ...s the P and buttons at the same time Display toggles between CAL and oFF 2 Press the P button Display shows previous dP selection STEP E Set the Decimal Point 1 Using the and adjust the display to the...

Page 7: ...unts and does not include the deci mal point If you need the decimal value with decimal point you will need to read the register convert it to decimal read 40024 see below to determine decimal locatio...

Page 8: ...ST2 Setpoint 2 Hysteresis setting 40019 0x0012 SINT16 R W 1999 9999 PRES3 Setpoint 3 setting 40020 0x0013 UINT16 R W 0 9999 HYST3 Setpoint 3 Hysteresis setting 40021 0x0014 SINT16 R W 1999 9999 PRES4...

Page 9: ...P2 Delay on Make doM Delay Time Setting STEP H Set the SP2 Delay on Break dob Delay Time Setting STEP I Set the Hysteresis Setting for Setpoint 2 1 Using the and buttons adjust the display to the desi...

Page 10: ...with external signal OFF 17 16 19 19 18 MANUAL rescaling ON AUTO scaling OFF ON SP1 NO SP1 NO SP2 NO SP2 NO Pins 14 and 15 AC DC Power Input Auto sensing AC DC power supply For voltages between 85 265...

Page 11: ...air circulation 3 Separate input output leads from power lines to protect the meter from external noise Input output leads should be routed as far away as possible from contactors control relays tran...

Page 12: ...71 1 8 DIN Cutout spacers 87 4mm 3 45 Various bezel colors are available Black is standard Prog SP3 SP4 SP2 SP1 For additional strength extra Mounting Slide Clips can be ordered and doubled up one beh...

Page 13: ...se is made from fire retardant polycar bonate A metal surround case can be ordered to enhance the meter s fire retardant capabilities and also provide shielding against electromagnetic interference EM...

Page 14: ...OA____ DL 40JANUS SG Add to the basic model number the order code suffix for each standard option required The last suffix is to indicate how many different special options and or accessories that you...

Reviews: