background image

Texmate, Inc. Tel. (760) 598-9899  •  www.texmate.com

Page 4

Apr-21-2016 DI_602A 320 DS (NZ313)_April 2016

Block Diagram of the Tiger 320 Series Software and Hardware Structure

RESIDENT TIMER 1
RESIDENT TIMER 2

Runs ONLY if selected on CH3,
or CH4.   Resolution 1 sec

I2C 
BUS

LOGIC I/O

FROM 

MODULES

Prescaler
Channel 1 & 2

17 BIT ON BOARD

DUAL SLOPE A to D

REF IN

CHANNELS

RESULT

CHANNEL

1

2

3

4

CHANNELS 1

2

1

2

3

4

1

R

R

2

3

4

1

R

D

D

2

3

4

1

R

DEFAULT

DISPLAY

CHANNEL

DEFAULT

DISPLAY

CHANNEL

2

3

4

DISPLAY FORMATTING

 

I2C

MICRO

Sigma Delta

A to D

16 to 24 Bit

Signal

Conditioning

REF

SSR SSR

REF

Sig

Con

SMART MODULES WITH MULTICHANNEL INPUTS,

AN ON-BOARD A TO D CONVERTER,

MICROPROCESSOR, AND TWO 
SOLID STATE RELAY OUTPUTS

Signal

Conditioning

MULTI-INPUT MODULES

W/DIGITAL SCALING

MUX

REF

PULSE

Signal

Conditioning

SINGLE INPUT MODULES

WITH ANALOG SCALING

REF

ZERO

SPAN

Signal

Conditioning

REF

RAW DATA                   

ANALOG, DIGITAL

                                       

AND LOGIC I/O

MACRO PROCESSING

DATA LOGGING

Manual or auto, Up to 4000 

samples, Date and Time 

stamp, endless loop record, 

Burst downloading

SERIAL COMMUNICATION

Read and write into all registers

ASCII, MODBUS,
Meter TO Meter Communication,
ETHERNET (TCP/IP), Epson Compatible
Serial Printer Driver

SETPOINTS

Up to 6 relay, SSR,
TTL or open collector.
PID, deviation, trigger, pulse,
tracking, hysteresis, latching,
timer modes, reset,
High/low/deviation activation

TOTALIZER 1
TOTALIZER 2

Two independent totalizers

Linearizing

4 Tables of 32 Points each
or 1 Table of 125 Points

Internal System Clock

Downloads from Real Time Clock
or starts from 12:00 on power up.
Can be displayed on CH3, CH4

Optional Real-time clock
with date and time stamp

Rear Pins

Hold, Test, Lock & Capture.

The Lock, Hold and Capture 

pins can be reprogrammed
for use as Digital Logic I/O pins.

 

ANALOG OUTPUT

Voltage or current, 

single or dual

PLUG IN OPTO-ISOLATED
I/O 6 IN 6 OUT OR 6 IN 16 OUT

DISPLAY DRIVE

SMART MODULES WITH AN ON BOARD

MICROPROCESSOR AND TWO SOLID STATE

RELAY OUTPUTS WITH PULSE, OR QUADRATURE

ENCODER INPUTS FOR COUNTING, FREQUENCY OR POSITION

I2C

MICRO

Signal

Conditioning

SSR SSR

REF

Sig

Con

Signal

Conditioning

 

Cross Channel Math 

 1+2, 1-2, 1x2, 1/2, 1=R

RESET 

with UP/DOWN

Peak, Valley,

Tare, Totalizers

VIEW MODE

to view 

selected

function values 

P and UP Buttons

to enter setup

menu.

P and DOWN 

Buttons to enter 

setpoint menu. 

PROGRAM

BUTTON

MACRO_

PROCESSING

Including

EDIT MACRO

F1_BUTTON

MACRO_

PROCESSING

F2_BUTTON

MACRO_

PROCESSING

F3_BUTTON

MACRO_

PROCESSING

ON DEMAND
FUNCTIONS
Hold down the
 PROGRAM 
button for 4 secs 
to initiate Auto 
tare, Auto 
Calibration,
Manual Loader or
Input Channel 
Compensation

PROGRAM LOCK 

If Program lock is ON values are 

displayed, but cannot be changed

SETPOINT LOCK 

If Program lock is ON values are 

displayed, but cannot be changed

Prog

F1

F2

F3

RESULT PROCESSING

of Cross Channel Math

Select data source for

 

OUTPUT PROCESSING

Select data source for: Setpoint 1, 2, 3, 4, 5, 6; 
Analog output 1, 2; Data logging

                                        

Select data source for 

DISPLAY PROCESSING

Select data source for: 
Display 1 (Default Display Channel D), Display 2, 
Display 3, Peak, Valley, Totalizer 1, Totalizer 2,

        

AVERAGING, 
CALIBRATION (SCALE and OFFSET),
INVERSE OF INPUT, LINEARIZATION, 
LOG OF INPUT (Bargraph display only)
RTD, SAMPLE RATE, SMART AUTO ZERO,
SQUARE ROOT,  THERMOCOUPLES

DECIMALS, , RIGHT HAND CHARACTER, AND ROUNDING 
FOR CH1, 2, 3, 4, RESULT AND DEFAULT DISPLAY

CUSTOM TEXT FOR CH1, 2, 3, 4, RESULT, PEAK, VALLEY,
TOTALIZER 1, TOTALIZER 2, SP1, SP2, SP3, SP4, SP5, SP6

DIGITAL PROCESSING

Select from R, 1, 2, 3, 4, Totalizer 1, 2, Peak, 
Valley, Tare or any usable registers from 1 to 244

        

Select from R, 1, 2, 3, 4, Totalizer 1, 2, Peak,
Valley, Tare or any usable registers from 1 to 244

        

Code1

SPC_1 to 6

SPC_1 to 6

Code1

Code7

   

Code2

Code4

Code5

Code6

Code8

CAL

CAL

CAL

CAL

CAL

CAL

CAL

CAL

Linearization

24 bit registers in EEPROM that store 
the four 32 point LIN tables.

 

Registers 257 to 512

OPERATING SYSTEM USE ONLY

DO NOT write to these registers, as 
any alteration to their data may make
the meter inoperative.

Registers 1125 to 2048

OPERATING SYSTEM USE ONLY

DO NOT write to these registers, as 
any alteration to their data may make
the meter inoperative.

Registers 4097 to 5120

Multi function, multi type Registers 
that may only be accessed through 
the serial port or by macros. Their 
functions are detailed in the Register 
Supplement.

Registers 513 to 1124

Macro Code Storage

16 bit unsigned. In Flash RAM

Registers 2049 to 4096

16 bit unsigned. May be 
accessed by macros or 
Serial Port.

Registers 5120 to 6144

Code9

Code5

Code6

FLASH

Result of Cross

Channel Math

AVERAGING, CALIBRATION (SCALE & OFFSET),  
INVERSE of R, LOG OF R (Bargraph display only)
 

 

       LINEARIZING of R, 

 

 

       SMART AUTO ZERO,

                                          SQUARE ROOT of R,

SP1

SP2

SP3
SP4

SP5

SP6

Registers 1 to 244

Registers from 1 to 244 may be selected

manually as a data source for setpoint 

or output processing. However only 

those registers shown below contain 

data applicable for use as data source.

Setpoints

6 to 11- SP1,2,3,4,5,6 value

65 to 70- SP1,2,3,4,5,6 Hysteresis,

71 to 76- delay on make SP1,2,3,4,5,6

77 to 82-  delay on break SP1,2,3,4,5,6

Input Channels

18,19,20,41,42- Raw Result,CH1,2,3,4

21 to 23,43,44- Scaled Result,CH1,2,3,4

45,46- Prescaler CH1,2

 

Smart modules

54 to 60- Smart Output 1,2,3,4,5,6,7

Analog Outputs

83, 84 - Analog Output 1 & 2

Variables (Used with Macro Only)

85 to 94 - Variable 1 to Variable 10

Timers

95 & 96 - Timer 1, 2

Real time Clock

213 to 219 - Real Time Clock

Auto Zero Offset

227 to 231 - Auto Zero Offset for Result,

CH1, CH2, CH3 & CH4

Operating System 

NOT USABLE as a data source. 

15,38,47,48,52,53,61-64,123-128,140,

141,160,161,234-244

6144 REGISTERS

  

Registers are comprised of 8, 16 or 

32 bit signed, unsigned or floating 

point registers, implemented in either 

Flash RAM, RAM, FeRAM, EEPROM 

or NVRAM (Real time clock option).

   See the Register Supplement for 

detailed information on ALL registers

   All registers may be accessed, and 

read or written to via the serial port, 

and by user developed macros.

   

  The registers used for the operating 

system should not be written into, as

modification of their data may render

the meter inoperative.

LOG BARGRAPH DISPLAY, dB DISPLAY, OCTAL.

BRIGHTNESS, ANNUNCIATORS, TREND

SCALE, OFFSET FOR CH1, 2, 3, 4 AND RESULT

A macro can access all functions and read
and write into all registers. Macro Timer1,
Macro Timer2 have 0.1 second resolution.
Macros allow a user to customize a meter
for a specific application using the Tiger 320
Development System. Macros may be locked
to prevent access by anyone.

ANALOG, DIGITAL
AND LOGIC I/O

Summary of Contents for Tiger 320 DI-602AE

Page 1: ...weighing applications Programmable input averaging and smart digital filtering for quick response to input signal changes Display text editing Customize display text for OEM applica tions Scrolling d...

Page 2: ...ts with fully configurable hysteresis on and off delays one shot pulse and repeat timers latching dual PID set point tracking resetting of registers initiating of logging and printing Signal Condition...

Page 3: ...ut Fully scalable from 4 to 20mA or 0 to 20mA or reverse and selectable for 0 to 10VDC or reverse 2 Dual Analog Output Fully scalable from 0 to 10VDC or reverse Outputs continued Analog Output Specifi...

Page 4: ...INVERSE OF INPUT LINEARIZATION LOG OF INPUT Bargraph display only RTD SAMPLE RATE SMART AUTO ZERO SQUARE ROOT THERMOCOUPLES DECIMALS RIGHT HAND CHARACTER AND ROUNDING FOR CH1 2 3 4 RESULT AND DEFAULT...

Page 5: ...Page 5 Apr 21 2016 DI 602A 320 DS NZ313 _UL_April 2016 Texmate Inc Tel 760 598 9899 www texmate com THIS PAGE INTENTIONALLY LEFT BLANK...

Page 6: ...When the function button is pressed the macro carries out its designated tasks See Display with Faceplate and Bezel diagram Annunciator LEDs The annunciator LEDs can be programmed to indicate the alar...

Page 7: ...the respective pins have to be connected to the COMMON pin pin 11 The LOCK pin can also be configured in Code 9 to carry out the fol lowing functions see Front Panel Programming Codes on Page 9 Reset...

Page 8: ...etting 000 is shown If an X appears in place of a digit this means that any number displayed in that digit is not relevant to the function being explained or more than one selection can be made SP1 SP...

Page 9: ...t 3 SP_3 Setpoint 4 SP_4 Setpoint 5 SP_5 Setpoint 6 SP_6 Enter these menus to adjust SP activation values Setpoint Relay Control Settings Mode P P P P P Setpoint 1 SPC_1 Setpoint 2 SPC_2 Setpoint 3 SP...

Page 10: ...function in the Calibration On Demand Mode press the P button for 4 seconds to activate one of the following selected on demand modes On Demand Modes Tare Single point calibration Two point calibrati...

Page 11: ...g are hidden preventing them from being reprogrammed Any codes that have not been blanked out are still visible and can be reprogrammed Turning code blanking OFF means all meter programming codes are...

Page 12: ...ness Mode Adjust brightness to 7 OR SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 Operational Display Press at same time SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 SP1 SP3 SP4 SP5 SP6 SP2 F1 P...

Page 13: ...odule Note This function is not available on all input modules 5 Calibrate Analog Output requires multimeter con nected to pins 16 and 17 6 7 0 Serial Communications Properties 1 Set Auto Zero Mainten...

Page 14: ...1 to 255 samples The averaging window can be set to between 1 and 65535 counts See the calibration modes diagram on Page 13 showing a breakdown of 1st 2nd and 3rd digits See Input Signal Sampling Sho...

Page 15: ...P5 SP6 SP2 F1 P F2 Operational Display Press at same time SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 Press 1 OR SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 Press 1 SP1 SP3 SP4 SP5 SP6 SP2 F1...

Page 16: ...g window settings Example INPUT SIGNAL 1st Digit 2 Selects related calibration functions 2nd Digit 2 Selects averaging samples for 3rd digit 3rd Digit 1 Selects CH1 for 2nd digit Enter Brightness Mode...

Page 17: ...in Code 1 CODE 1 Display Configuration Modes All meter display modes except the display brightness mode are configured in Code 1 See diagram below See Code 1 diagram on Page 18 for a breakdown of firs...

Page 18: ...e meter the values for setpoint 5 and setpoint 6 are activated as upper and lower limits See Analog Output Supplement for further details Note 1 LED annunciators are always off except when the meter i...

Page 19: ...re the Primary Display with the display diSP as the data source by setting Code 1 to X50 See diagram at the bottom of the page for data source selection options Configure Data Source Procedure The fol...

Page 20: ...SP5 SP6 SP2 F1 P F2 Press 1 0 No rounding 1 Rounding by 2 s 2 Rounding by 5 s 3 Rounding by 10 s Configure Display Format Mode Procedure LAST DIGIT ROUNDING DISPLAY UNITS 0 Decimal 1 24 hour clock mod...

Page 21: ...rational Display Press at same time SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 Press 2 OR SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 Press 1 SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 OR SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 Press 1 SP1 SP...

Page 22: ...and enter Code 2 SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 Operational Display Press at same time SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 Press 2 OR SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 Press 1 SP1 SP3 SP4 SP5 SP6 SP2 F1 P...

Page 23: ...TD 2 or 4 wire 3rd digit selects type of RTD 4 Frequency 5 Period 6 Counter 7 Smart Input Module CODE 2 CHANNEL 1 MEASUREMENT TASK AND SAMPLING RATE SMART INPUT MODULE 0 Output Register 1 1 Output Reg...

Page 24: ...me stamp Time stamp settings are configured in Code 8 Post processing functions refer to functions that occur to the input after it has been configured and scaled Example Procedure Configure the meter...

Page 25: ...st and 2nd digits of Code 4 The diagram opposite lists the available configuration selections in Code 4 Example Procedure Configure CH2 for a voltage input direct with no linearization by setting Code...

Page 26: ...ut by setting Code 5 to 11X FOR THERMOCOUPLE 0 Type J 1 Type K 2 Type R 3 Type S 4 Type T 5 Type B 6 Type N 7 Select user defined lineariza tion table Table 1 set up in CAL 24X FOR RTD TYPE 2 3 4 WIRE...

Page 27: ...le 3rd digit selects register FOR SMART INPUT MODULE 0 Output Register 1 1 Output Register 2 2 Output Register 3 3 Output Register 4 4 Output Register 5 5 Output Register 6 6 Output Register 7 7 Smart...

Page 28: ...Note 5 5 125 point Linearization on Result Tables 1 to 4 cascaded See Note 5 6 32 point Linearization on Result Tables 1 to 4 selected from the rear of the meter The selected table is not available if...

Page 29: ...ONS LOG OR PRINT TRIGGER 0 No trigger 1 Trigger on Demand from PROGRAM Button 2 Trigger on Demand from F1 Button 3 Trigger on Demand from F2 Button 4 Trigger on Demand from HOLD Pin 5 Trigger on Deman...

Page 30: ...of the meter and the selected input module Relay Output Modules Four standard relay output module options provide a selection of 16 relay configuration options for DI 50 meters Three electromechanica...

Page 31: ...s Setpoint Reset Trigger Setpoints can be programmed to reset selected registers or be manually reset They can also trigger a data print or a data log Dual PID SP PID Control Settings The PID proporti...

Page 32: ...Pulsed OFF Modes These are delay modes were the relay is normally on and pulses off when the setpoint activates 1 Shot OFF mode Programmable Minimum OFF time SP OFF SP ON 1 Shot OFF Mode Prog Min OFF...

Page 33: ...P F2 SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 OR SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 Press 1 SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 Press 1 SP1 SP3 SP4 SP5 SP6 SP2 F1 P F2 SP1 SP3 SP4 SP5...

Page 34: ...rgized BELOW setpoint value with RISING INPUT SIGNAL INITIAL START UP INHIBIT SP Activation Source 0 Activate Setpoint Source from Selected Register 1 Select Source for Setpoint Note X1X is a register...

Page 35: ...0 to 6553 5 secs Reset SPC_X to XX0 DOM 0 0 to 6553 5 secs Minimum on time M_on 0 0 to 6553 5 secs On time on _t 0 0 0 001 to 6553 5 65 535 secs DOB 0 0 to 6553 5 secs Off time oFF_t 0 0 0 001 to 655...

Page 36: ...hold the button down while cycling through the decades and release it when oFF or tArE appears Registers that Should Not be Used The following registers are contained within the selectable 1 to 244 R...

Page 37: ...ltage Isolated Feed Back Isolated Switching Power Supply Controller 5 VDC 18 VDC ISO 5 VDC 5 VDC 5 VDC GND 24 VDC GND LC Filter 1 2 3 4 5 6 7 8 9 10 RELAY MODULES NO3 COM 1 3 NO1 NC1 NO4 COM 2 4 NO2 N...

Page 38: ...3 SP1 SP4 SP2 Relay Modules with up to two 4 5A Form A Relays and up to two 9 10A Form C Relays 32 31 30 28 29 27 26 25 Options Order Code OR51 OR52 OR53 OR54 210mA 210mA 210mA 210mA 210mA 210mA 210mA...

Page 39: ...and process control applications Modular construction ensures you don t have to pay for unnecessary hardware Simply order the input and output options to suit your application Input Signal Conditioni...

Page 40: ...optional Analog Output Module optional Relay Output Module and a Serial Output Module RS 232 RS 485 or No Serial Output Ethernet Output Carrier Board Is similar to the Standard Output Module Carrier B...

Page 41: ...noisy components Shielding cables for input output leads is recommended with shield connection to earth ground near the meter preferred 4 A circuit breaker or disconnect switch is required to disconne...

Page 42: ...Code 3 Channel 1 Post Processing and Serial Mode Functions 24 Code 4 Channel 2 Measurement Task and Sampling Rate 25 Code 5 Channel 3 Functions 26 Code 6 Channel 4 Functions 27 Code 7 Result Processi...

Page 43: ...d Not Be Selected 36 Resetting and Incrementing Using Setpoints 36 Relay Logic Output Modules 38 Serial Communication Configuration 24 Pinouts 38 Setpoint Programming Mode 30 35 Data Logging 31 Data P...

Page 44: ...om Texmate has facilities in Japan New Zealand Taiwan and Thailand Case Dimensions Clear Lockable NEMA 4X Splash Proof Cover P N OP N4 96x48 The 96x48mm case is particularly suitable for mounting in m...

Reviews: