background image

IntelliPack Series 892M/894M Computation Transmitter User's Manual                             DC Voltage/Current Input 
___________________________________________________________________________________________ 
 

 - 7 - 

 

Table 3B:  Int

elliPack 89xM Math Functions…continued 

FUNCTION 

DESCRIPTION 

OR(n1,n2,..,n5)

 

Conditional construct OR of two to five 
channels, numbers, or expressions.  
True if any one or more of n1..n5 are 
true.  Can only be used inside the 
conditional expression for IF. 

Conditional construct -less than.   

<= 

Conditional construct -less than or equal 
to. 

Conditional construct -greater than. 

>= 

Conditional construct -greater than or 
equal to. 

Conditional construct -equal to. 

<> 

Conditional construct -not equal to. 

 
Notes (Table 3): 

1.   In the table, “

n

” is used to represent a channel variable, 

number, or expression (another function or equation). 

2.   Do not use the plus symbol as a polarity indicator, it is only 

used for the add operation. 

3.   Do not type or embed space between the sign of a number 

and the number itself. 

4.   Do not type or embed space between the function keyword 

and left parenthesis. 

 

Show Simulator 

 

The IntelliPack Configuration Software also provides a Show 

Simulator function that you can use to test your formula and 
ensure that a correct output response within range is produced, 
without having to drive the inputs with real world signals.  For 
each input, a slider control is provided to simulate the input 
signal.  For fine control of the slider, use the left and right arrow 
keys.  The corresponding output value is displayed using scaled 
units, and signal units (voltage or current).   Error checking in this 
area is limited and it is up to the user to verify correct output 
formulation for all possible conditions of input.  As such, use of 
the Show Simulator function is highly recommended for critical 
control applications.  Computations that return values beyond the 
defined range will be “clipped” to the minimum or maximum 
scaled values to ensure that a valid output response is always 
returned. 

 
The following example equations are entered into the 

Equation field exactly as they are shown below. 
 

Equation Examples 

 
Compute the average of 4 signals -  

(A + B + C + D)/4 

 
Compute the smallest square root of 3 input signals -

MIN(SQRT(ABS(A)), SQRT(ABS(B)), SQRT(ABS(D)))  

 
Compute the square of the scaled value of channel 1 - 

POWER(A,2) 

 
Compute the sum of the minimum and maximum of 4 signals - 

MIN(A, B, C, D) + MAX(A, B, C, D) 

 
Compute the maximum of 4 different signals greater than 10 -

MAX(A, B, C, D, 10) 

 
Conditional expression examples - 

IF(AND(A>B,C=D)) THEN(A*2) ELSE(B*3) 

 

IF(OR(A>=B,A=D)) THEN(A) ELSE(C) - 12.56 

 

When formulating an equation or response, it is important to 

keep the limits of module resolution in mind (see Table 5).  In 
some cases, it may be necessary to normalize your variables or 
output response.  Always use the Show Simulator function to test 
your equation over the full range of input to ensure a valid output 
response.  A computation that returns a value beyond the defined 
range will be “clipped” to the minimum or maximum scaled values 
to ensure a valid response is always returned.  Due to memory 
constraints of the module, some equations may be too complex 
and an error will be indicated in the Show Simulator screen. 
 

HOLD Function 

 

This module also includes a HOLD input terminal that affects 

the output response.  With HOLD deasserted (set HIGH or left 
open with respect to COM terminal), the output will track the 
result of the input equation.  However, if HOLD is asserted (set 
LOW or shorted to COM), then the output will remain at the result 
of the last computation until HOLD is deasserted.  Note that the 
input HOLD signal is driven with respect to input COM.  Input 
COM and RTN are not the same potential and should never be 
connected together, either directly or through ground.  Do not 
ground COM. 
 
 

4.0  THEORY OF OPERATION 

 

Refer to Simplified Schematic 4501-717 and Functional Block 

Diagram 4501-718 to gain a better understanding of the circuit.  
Note that this transmitter will pre-filter a signal and convert the 
signal to a scaled voltage--either through a voltage divider circuit 
(voltage input), or a current sink resistor (current input).  An A/D 
converter stage then applies appropriate gain to the signal, 
performs analog-to-digital conversion, and digitally filters the 
signal.  The digitized signal is then transmitted serially to a 
microcontroller.  The microcontroller completes the transfer 
function according to its configuration and programmed equation, 
and then sends a scaled output signal to an optically isolated 
Digital-to-Analog Converter (DAC).  The DAC then updates its 
current or voltage output in response.  If HOLD is asserted, then 
the output will remain at the last value until HOLD is deasserted.  
With HOLD deasserted (set HIGH or left open), the output will 
track the result of the input equation.  The embedded 
configuration and calibration parameters are stored in non-volatile 
memory integrated within the microcontroller.  Only the functions 
required by an application are actually stored in memory

—new 

functionality can be downloaded via the IntelliPack Configuration 
Program and Serial Port Adapter.  A wide input range switching 
regulator (isolated flyback mode) provides is5V and +16V 
power to the circuit, plus an is15V output circuit supply. 

 

Summary of Contents for IntelliPack 895M Series

Page 1: ...cess Current Voltage Inputs USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1998 Acromag Inc Printed in the USA Data and...

Page 2: ...NT are registered trademarks of Microsoft Corporation 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter models listed in Table 1 Supplementary sheets are attached fo...

Page 3: ...ash memory and EEPROM This allows the functionality of this device to be reliably reprogrammed thousands of times Fully Isolated Input output and power are isolated from each other for safety and incr...

Page 4: ...ically protected with an anti static bag during shipment However it is recommended that the module be visually inspected for evidence of mishandling prior to applying power This circuit utilizes stati...

Page 5: ...trical Code for installations within Canada and in accordance with the authority having jurisdiction This equipment is suitable for use in Class I Division 2 Groups A B C and D or non hazardous locati...

Page 6: ...solution must also be scaled to the nominal zero and full scale endpoints of the selected output range Up to 200 characters may be entered into the equation field to define a formula that relates the...

Page 7: ...A B A D THEN A ELSE C 12 56 When formulating an equation or response it is important to keep the limits of module resolution in mind see Table 5 In some cases it may be necessary to normalize your va...

Page 8: ...ir services are available from Acromag 6 0 SPECIFICATIONS 892M 0500 C Two I V Inputs Single Process I V Output 894M 0500 C Four I V Inputs Single Process I V Output General The IntelliPack Model 89XM...

Page 9: ...LSB 8 4 20mA DC 16797 953nA LSB 2 0 5V DC 26298 190uV LSB 1 0 10V DC 26298 380uV LSB IMPORTANT Input COM and RTN are not the same potential and should never be connected together either directly or th...

Page 10: ...t exceed 36VDC peak to avoid damage to the module Table 8 89XM Supply Current Supply Voltage Supply Current SPA Connected Supply Current SPA Not Connected 10V 330mA 300mA 12V 250mA 230mA 15V 200mA 175...

Page 11: ...al EXP natural logarithm LN logarithm base 10 LOG10 power POWER sine SIN cosine COS tangent TAN arc sine ASIN arc cosine ACOS and arc tangent ATAN Support for IF THEN ELSE plus AND OR constructs are i...

Page 12: ...N I3 2 2 2 3 2 6 2 5 2 4 I4 V4 RTN INSTAL L V TO I JUMPER AT INPUT FOR CURRENT INPUTS TRANSIENT VOL TAGE AND NOISE SUPPRESSION DEVICES ARE NOT SHOWN 4 9 9 4 9 9 K 5 4 9 K 1 6 VOL TS 4 9 9 5 4 9 K SERI...

Page 13: ...LO Y LO Y H I Y X XL YH YL XH XL YL X LO X H I ANALOG INPUT X In pu t Sen s o r Ty p es Vol tag e DC M i l l i am p ere s DC AC Curren t wi th AC Se ns or I nput 1 2 Cal Val u e Cal HI Cal LO Val u e...

Page 14: ...ONFIGURATION RUNNING WINDOWS 95 OR NT S E E USE R S MA NUA L MODULE CONFIGURA TION CONFIGURA TION P ORT FOR POWER RUN PWR LE D GREE N OV ERRA NGE LE D s YE LLOW 10 TO 36VD C TB4 A cromag R U N I N P U...

Page 15: ...H HOLD DEASSERTED HI G H OR OPEN THE OUTPUT W I L L TRACK I N PUT CHANGES HOLD I S ASSERTED LOW AND W I L L HOLD THE TRANSM I T TER OUTPUT AT THE LAST VALUE SHI EL DED CABL E TB1 CURRENT J UM PER V2...

Page 16: ...____________________________________ 16 Acromag R U N 1 2 3 4 INPU T STATU S 118 9 4 68 95 3 3 75 R 2 34 59 4 DIN EN 5 0 0 2 2 3 5 mm T RAIL DIN MO UNTING C L SCREWDRIVER SL O T FO R REMO VAL FRO M T...

Page 17: ...________________________________________________ 17 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017...

Reviews: