Publication 1734-UM006B-EN-P - August 2005
Access Instantiated Instances
5-3
Assemblies
Available assemblies are:
•
Assembly 101 is produced for a polled connection.
•
Assembly 102 is produced for a Change Of State (COS)
connection.
•
Assemblies 103, 104 and 106 are by Explicit message only.
•
Assembly 105 is consumed in a polled connection .
Data may be read (get) or written (set) using an Explicit Message. For
example, to read the Present Channel Data, assembly 101
10
(65
16
) can
be requested.
Data is ordered as followed (byte 0 is the least significant byte):
8 bit byte
Byte 0
16 bit word
Byte 0, byte 1
32 bit long word
Byte 0, byte 1, byte 2, byte 3
In this example, assembly 101,
Service
Class
Instance
Attribute
0E (Get)
04 (Assembly)
65 (Present Data)
03 (Data Attribute)
Instances
Services
Field
Bytes
#101
(0x65)
Get
Present Channel Data
4
Status
2
#102
(0x66)
Get
Stored Channel Data
4
Status
2
#103
(0x67)
Get
Present Channel Data
4
Stored Channel Data
4
Status
2
#104
(0x68)
Get
Programming Error Code
2
#105
(0x69)
Set/Get
Counter Control
1
AB Drives